1-2
Chapter 1: Module Overview
User’s Manual Pub. 0300306-02 Rev. B
The 2085sc-IF16C/V Expansion I/O modules measure current or voltage input
data. The module supports:
•
Sixteen input channels.
•
2085sc-IF16C module: Current measurements. The module measures the
channel input current across a low-drift precision resistor, measures the
voltage,
and converts the voltage to a current reading.
•
2085sc-IF16V module: Direct voltage measurements. There is no low-drift
precision resistor installed, and the channel accepts the voltage source
directly.
•
Open-wire detection (voltage ranges and current 4-20 mA range).
•
Range scaling of input data.
•
High and low process alarms that provide a warning on under- or over-range
detection (from user-defined values).
•
Four data formats.
•
Four filter frequency setup.
•
Disabling open-wire detection for any, or all, channels.
All inputs have fault tolerance and ESD protection to avoid damage to circuitry
on the board. The modules use 50 VAC working Reinforced Insulation between
the inputs and the backplane. Individual channels are not isolated from each
other.
The 2085sc-IF16 modules use two sets of 20-bit Sigma-Delta analog-to-digital
converters to achieve a 16-bit resolution. The modules digitally convert and store
analog data from either the current or voltage input type. Each input channel is
individually configured via Rockwell-provided Connected Component
Workbench (CCW) software for the Micro850 and Micro870 family of PLC
controllers, or with the Module Configuration Converter utility from Spectrum
Controls, Inc.
The module is factory calibrated and tested before shipping. After installation,
the modules begin operation in a default, usable condition:
•
The default configuration for the 2085sc-IF16C is for all channels enabled in
the 4 to 20 mA range with the 17 Hz filter in Engineering ×1 units.
•
The default configuration for the 2085sc-IF16V is for all channels enabled in
the
±
10 V range with the 17 Hz filter in Engineering ×1 units.
Section 1.2
Input Specifications
The 2085sc-IF16C/2085sc-IF16V modules have the following input
specifications:
Table 1-1 Input/Performance/Environmental Requirements
Input Description
Value
Operating Temperature
-20 ºC to 65 ºC (-4 ºF to 149 ºF)
Storage/Non-Operating
Temperature
-40 ºC to 85 ºC (-40 ºF to 203 ºF)
Operating Humidity
5% to 95%, non-condensing
Summary of Contents for Micro800 2085sc-IF16C
Page 1: ...User s Manual Pub 0300306 02 Rev B...
Page 8: ...vi Micro800TM 16 Channel Analog Input Module User s Manual Pub 0300306 02 Rev B...
Page 18: ...1 10 Chapter 1 Module Overview User s Manual Pub 0300306 02 Rev B...
Page 54: ...3 28 Chapter 3 Configuring the 2085sc IF16 Using CCW User s Manual Pub 0300306 02 Rev B...