background image

Summary of Contents for 1762sc-IF4OF4

Page 1: ......

Page 2: ...or service referenced herein No patent liability is assumed by Spectrum Controls Inc with respect to the use of any of the information products circuits programming or services referenced herein The...

Page 3: ...rations 2 2 2 3 1 Prevent Electrostatic Discharge 2 3 2 3 2 Remove Power 2 3 2 3 3 Selecting a Location 2 3 SECTION 2 4 MOUNTING 2 4 2 4 1 Minimum Spacing 2 4 2 4 2 DIN Rail Mounting 2 4 2 4 3 Panel M...

Page 4: ...to install configure program operate and troubleshoot a control system using the 1762sc IF4OF4 Related Documentation The table below provides a listing of publications that contain important informati...

Page 5: ...pe is used for emphasis Bold type identifies headings and sub headings WARNING Identifies information about practices or circumstances that can lead to personal injury or death property damage or econ...

Page 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...

Page 7: ...iption The combo supports current voltage and thermocouple input types and current or voltage output types The module digitally converts and stores analog data from any of the three input types mentio...

Page 8: ...and Ranges The table below lists the input types and their associated ranges Table 1 2 Input Types Input Type Range E Type Thermocouple 200 to 1000 C 328 to 1832 F J Type Thermocouple 180 to 1200 C 2...

Page 9: ...ferent filter frequencies 4 Hz 17 Hz 62 Hz 470 Hz Section 1 6 Hardware Features Channels are wired as differential inputs or single ended outputs One cold junction compensation CJC sensor comes instal...

Page 10: ...l latch 9 Pull loop 10 Ch 6 and Ch 7 DIP switch Voltage Current selection Shipped with current selected DIP switches in Down position as shown 1 6 1 LED Indicator The 1762 combo module uses a single g...

Page 11: ...or input output data not valid condition If such a condition is detected the channel data value will fail to a user defined state defined in the module configuration settings For more details refer to...

Page 12: ...1 6 Chapter 1 Module Overview User s Manual Pub 0300247 01 Rev D See the block diagram below ASIC...

Page 13: ...EMC and the following standards in whole or in part documented in a technical construction file IEC 61000 6 4 Electromagnetic compatibility EMC Part 6 4 Generic standards Emission standard for indust...

Page 14: ...components may impair suitability for Class I Division 2 Touch a grounded object to discharge static potential Do not replace components or disconnect equipment unless power has been switched off or...

Page 15: ...signal to your system s field devices causing unintended machine motion Causing an explosion in a hazardous environment Electric arcing causes excessive wear to contacts on both the module and its ma...

Page 16: ...50 8 mm 2 in of space on all sides for adequate ventilation as shown Figure 2 1 NOTE 1762 expansion I O may only be mounted horizontally WARNING During panel or DIN rail mounting of all devices be su...

Page 17: ...th extreme vibration and shock concerns use the panel mounting method described below instead of DIN rail mounting 2 4 3 Panel Mounting Use the dimensional template shown below to mount the module The...

Page 18: ...and the bus connector cover must be snapped in place In Class I Division 2 applications all modules must be mounted in direct contact with each other as shown in the graphic If DIN rail mounting is us...

Page 19: ...itter specifications Outputs Load resistance for a voltage output channel must be equal to or greater than 1 K Load resistance for a current output channel must remain between 0 and 500 Grounding WARN...

Page 20: ...ny other wiring and as far as possible from sources of electrical noise such as motors transformers contactors and ac devices Generally allow at least 15 2 cm 6 in of separation for every 120 V of pow...

Page 21: ...re under the terminal pressure plate You can use the stripped end of the wire or a spade lug The terminals will accept a 6 35 mm 0 25 in spade lug See Figure 2 5 3 Tighten the terminal screw making su...

Page 22: ...o module uses a single green LED to show operational status of the module The table below shows the possible blink codes Blink Code Description Blinks rapid green The module is not in run mode Solid G...

Page 23: ...You Should Know This chapter describes how to configure the IF4OF4 module for the MicroLogix 1100 1200 and 1400 system using RSLogix 500 programming software Section 3 2 Module Memory Map The module u...

Page 24: ...e describes how to add the IF4OF4 module to the RSLogix 500 programming software 1 Create a new RSLogix 500 project and select either a Micro 1100 1200 or 1400 processor 2 Double click I O Configurati...

Page 25: ...le within RSLogix 500 3 4 1 Output Data File Configuration Data The output data file is used to configure the advanced settings of the module including input type output type data format filter settin...

Page 26: ...on Register Input 2 High byte Channel 5 Configuration Register Input 2 O e 7 Low byte Channel 6 Configuration Register Input 3 High byte Channel 7 Configuration Register Input 3 1 See Table 3 2 2 See...

Page 27: ...67 11000 17202 11000 10 00 VDC High Range 29788 10000 16383 10000 10 00 VDC Low Range 29788 10000 0 10000 11 00 VDC Low Limit 32768 11000 819 11000 0 to 5 V 5 50 VDC High Limit 32767 5500 18021 11000...

Page 28: ...g F 1 3 4 4 Input Channel Configuration Channels 6 and 7 Channels 6 and 7 can be configured for current or voltage including thermocouple inputs The following table describes the configuration options...

Page 29: ...formats may yield the highest effective resolutions but may also require that you convert channel data to real engineering units in your control program Table 3 6 Input Channel Data Ranges Input Range...

Page 30: ...VDC High Range 10000 1000 32767 16383 10 00 VDC Low Range 10000 1000 32768 0 11 00 VDC Low Limit 11000 1100 32768 819 0 10 V 11 00 VDC High Limit 11000 1100 32767 17202 10 00 VDC High Range 10000 100...

Page 31: ...ut file is shown below Table 3 7 Input Data File Layout Word Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 General Status I e 0 S7 S6 S5 S4 S3 S2 S1 S0 Output Status I e 1 LD3 U3 O3 LD2 U2 O2 LD1 U1 O1 L...

Page 32: ...nt depending on the output type up to the High Limit value LD Load Error This applies only to output channels If the channel is configured for voltage this bit indicates a short circuit If configured...

Page 33: ...62 Hz 14 Hz 45 ms 17 Hz 4 Hz 135 ms 4 Hz 1 Hz 495 ms Getting Technical Assistance Note that your module contains electronic components which are susceptible to damage from electrostatic discharge ESD...

Page 34: ...3 12 Chapter 3 Configuring the 1762sc IF4OF4 for RSLogix 500 User s Manual Pub 0300247 01 Rev D...

Page 35: ...0 030 in max peak to peak Shock Operating 30 G Bus Current Draw max 30 mA at 5 VDC Max 3 4 W Max 140 mA max at 24 V Heat Dissipation 3 0 W Total Max Resolution 16 bits Integer Format Channel Update T...

Page 36: ...1 C UL under CSA C22 2 No 213 Operating Temperature Code T4a Radiated and Conducted Emissions EN61131 2 Electrical EMC The module has passed testing at the following levels ESD Immunity IEC61000 4 2 4...

Page 37: ...lters Normal Mode Rejection 4 Hz Filter 74 dB minimum at 50 and 60 Hz 17 Hz Filter 65 dB minimum at 50 and 60 Hz 62 Hz Filter First notch at 31 Hz typically 30 dB 470 Hz Filter First notch at 237 Hz t...

Page 38: ...mum System accuracy at 20 60 C 4 and 17 Hz filters Type J 180 C to 1200 C 5 0 degrees C maximum Type K 200 C to 1370 C 6 0 degrees C maximum Type E 200 C to 1000 C 4 5 degrees C maximum Type T 190 C t...

Page 39: ...acy at 25 C 4 and 17 Hz filters 20 uA maximum for 0 20 mA inputs 20 uA maximum for 4 20 mA inputs System accuracy at 20 C 60 C 4 and 17 Hz filters 50 uA maximum for 0 20 mA inputs 50 uA maximum for 4...

Page 40: ...es Current Output 380 nA per bit when using RAW format for all current ranges Differential Nonlinearity 1 LSB see resolution for LSB size Output Ripple 15 mV ripple for voltage or current Output Imped...

Page 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...

Page 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...

Page 43: ...tive 2 1 F Filter Frequencies 1 3 G Grounding 2 7 H Hazardous Location 2 2 I Input Data 3 9 Input Type 1 1 L LED 1 4 2 10 M Memory Map 3 1 Module Update Time 3 11 Mounting DIN 2 4 Panel 2 5 N Noise 2...

Page 44: ...User s Manual Pub 0300247 01 Rev D...

Page 45: ...User s Manual Pub 0300247 01 Rev D...

Page 46: ...ions subject to change without notice The Encompass logo and ControlLogix are trademarks of Rockwell Automation Corporate Headquarters Spectrum Controls Inc P O Box 6489 Bellevue WA 98006 USA Fax 425...

Reviews: