4-4
Chapter 4: Using Your Input Module
User’s Manual Pub. 0300128-04 Rev. A
Input Range (configuration bits 1–3)
Use this bit field to configure the channel for the type of input device you want to
connect to your module.
Data Format (configuration bits 4–6)
Use this bit field to select one of the following formats:
•
Engineering units (mV or nA).
•
Scaled for PID (works with the SLC PID instruction).
•
Proportional counts (two’s complement binary).
•
1746-NI4 compatible format (the format used by the 1746-NI4).
•
User-defined scale A.
•
User-defined scale B.
These data formats are defined in the following table.
Table 4-2. Data format definitions
Data Format
Selected
Input
Range
Actual Signal Limits Count Limits
Min.
Max.
Min.
Max.
Engineering
Units
±10 V
-10.25 V +10.25 V -10250
+10250
0–10 V
-0.50 V
+10.25 V -500
+10250
0–5 V
-0.50 V
+5.50 V
-500
+5500
1–5 V
+0.50 V
+5.50 V
+500
+5500
0–20 mA
0.0 mA
+20.5 mA 0
+20500
4–20 mA
+3.5 mA +20.5 mA +3500
+20500
Scaled for
PID
➂
±10 V
-10 V
+10 V
0
+16383
0–10 V
0 V
+10 V
0
+16383
0–5 V
0 V
+5 V
0
+16383
1–5 V
+1 V
+5 V
0
+16383
0–20 mA
0 mA
+20 mA
0
+16383
4–20 mA
+4 mA
+20 mA
0
+16383
Proportional
Counts
±10 V
-10.25 V +10.25 V -32768
+32767
0–10 V
-0.50 V
+10.25 V -32768
+32767
0–5 V
-0.50 V
+5.50 V
-32768
+32767
1–5 V
+0.50 V
+5.50 V
-32768
+32767
0–20 mA
0.0 mA
+20.5 mA -32768
+32767
4–20 mA
+3.5 mA +20.5 mA -32768
+32767
1746-NI4-
compatible
➀
±10 V
-10 V
+10 V
-32768
+32767
0–10 V
0 V
+10 V
0
+32767
0–5 V
0 V
+5 V
0
+16384
1–5 V
+1 V
+5 V
+3277
+16384
Summary of Contents for 1746sc-INI4i
Page 1: ...User s Manual Pub 0300128 04 Rev A...
Page 8: ...viii SLC 500 Isolated Analog Input Modules User s Manual Pub 0300128 04 Rev A...
Page 14: ...1 6 Chapter 1 Module Overview User s Manual Pub 0300128 04 Rev A...
Page 30: ...3 8 Chapter 3 Configuring the 1746sc INI4I User s Manual Pub 0300128 04 Rev A...
Page 44: ...5 4 Chapter 5 Programming Examples User s Manual Pub 0300128 04 Rev A...
Page 54: ...User s Manual Pub 0300128 04 Rev A...