Installation
10|2018 EN
21
5.4 Electrical
connection
WARNING
Risk of electric shock due to incorrect connections!
Electrical
connections
must always be carried out by
authorised specialists.
Observe
VDE
and
utility company regulations.
Install pumps for swimming pools and their protection
according to DIN VDE 0100-702.
Install a disconnecting device with at least a 3 mm contact
gap per pole to interrupt the power supply.
WARNING
Risk of electric shock due to voltage on the housing!
A built-in or external overload switch which is set correctly
must be installed for pumps with three-phase or A.C. motors
without motor protection. In doing so, observe the values on
the motor name plate.
Protect
power
supply
with a ground fault circuit interrupter,
nominal residual current I
FN
≤
30 mA.
Only use suitable pipe types according to regional
regulations.
Adjust
minimum
diameter of the electrical pipes to
accommodate the motor output and pipe length.
Do not bend or squash the pipes.
If hazardous situations can occur, provide an emergency off
switch according to DIN EN 809. The builder/operator must
make a decision according to this standard.
Connection by customer:
– Fuse protection 1-phase 230 V/3-phase 400 V safety fuse
16 A time delay or 16 A circuit breaker
– Short circuit breaking capacity I
CN
≤
6 kA
Summary of Contents for BADU Star 69/12
Page 3: ...DE DE Originalbetriebsanleitung Star Komplettfilter D41 04 009 P ...
Page 7: ...Inhaltsverzeichnis 10 2018 DE 5 10 2 Maßzeichnung 31 10 3 Kennlinie 32 11 Index 33 ...
Page 36: ......
Page 37: ...EN EN Translation of original operation manual Star Complete filter D41 04 009 P ...
Page 70: ...34 10 2018 ...