SV Series
Spa Controls
18
Sanitise Cycles
Automatic and manual water clean cycles
Press to activate sanitise cycle
Whilst the cycle is running the display alternates
between the W.CLN (water clean) title screen and
the minutes remaining in the cycle (refer above).
Sanitise Button
The sanitise button activates a twenty (20) minute sanitisation cycle that runs the
filtration pump and ozone / uv (if fitted) to filter the pool water to restore and refresh
water quality. With circ pump systems jet pump1 will also run for the full 20 minute
cycle. Where 2-speed filtration pumps are used the pump will run in high speed for the
duration of the cycle. In addition, at the start and end of the cycle, the controller will
sequentially (one at a time) run any additional pumps (pump2, pump3, pump4 if fitted)
and the blower for one minute each to purge the plumbing and clear any unfiltered
water trapped in those lines.
Press button to activate a 20 minute sanitise cycle
Press button again to cancel cycle (if desired)
IMPORTANT NOTES
•
When the cycle is started automatic mode is enabled and if running any additional
jet pumps and the blower are turned off.
•
If the controller falls within a designated sleep or power save period during a
sanitise cycle, the controller will not sleep until the sanitise cycle is finished.
Automatic Daily Sanitise Cycle
The controller will automatically run a 10 minute sanitise cycle every day at a user
adjustable time (Default = 9:00am). The automatic sanitise cycle works in the same
manner as a manual sanitise excepting that the cycle only runs for 10 minutes. This
feature cannot be disabled – only the time this cycle is activated may be changed via the
Setup Menu item W.CLN (refer pages 21 & 22).
IMPORTANT NOTES
•
If the controller is in a sleep period at the specified automatic sanitise cycle time, it
will wait until the sleep period ends before the sanitise cycle runs.
•
If the spa pool is in manual use (i.e. the loads have not timed out and the spa has
not returned to auto mode) at the time the automatic sanitise cycle is set to run
the cycle will be cancelled for that day.