background image

SV Series

 Spa Controls 

11

 

 

Adjusting Set Temperature Point

 

 

 

 

 

 

 

 

 

How to program the desired water temperature 

Press and hold                

OR

 

      Press                to confirm & save 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The SV series spa controllers have been designed with simplicity in mind. The intelligent software 
constantly monitors the spa water, automatically controlling the heater and/or heat pump (if 
fitted) to ensure the desired set water temperature is maintained and required level of daily 
filtration achieved.  
 
With set-and-forget technology, the spa user simply selects their desired water temperature 
(Range: 10

o

C - 41

o

C; Default: 38

o

C) and thereafter the SV controller will automatically heat to and 

maintain that selected water temperature. This is called demand heating - the filtration pump and 
heater will be activated as required to maintain the set water temperature. The time spent heating 
the spa and running the pump under normal operation will be taken into account and where 
required the filtration pump will run for additional periods throughout the day to maintain the 
minimum level of daily filtration.   
 
Dependant on the amount of normal spa use, set water temperature, daily filtration times, and 
climatic conditions being experienced, the SV controller will engage the heater and/or heat pump 
(if fitted) for differing periods of time, at differing times of day. The advanced software constantly 
monitors and recalculates after each heating / filtration cycle to ensure the correct daily filtration 
time is achieved and desired set water temperature is maintained. 
 
Unless adjusted the SV controller will automatically heat to and maintain the default temperature 
of 38

o

C. The water temperature set point can be adjusted from 10

o

C to 41

o

C in steps of 0.2

o

increments.  
 

Press and hold                or                to begin set temperature point adjustment 

 

The keypad numbers will flash during temperature adjustment 

 

Once desired set temperature point has been selected press                to confirm 

 

 IMPORTANT NOTES 

 

 

During a heating cycle the SV controller may raise the water temperature up to 0.6

o

C above 

set temperature point to provide an average water temperature of set point at most times. 

 

 

UUIf an optional heat pump is NOT fitted

 the spa controller has 

NO

 ability to cool the spa 

water. Lowering the set temperature point will NOT cause the water to cool.  

 

 

If an optional heat pump IS fitted

 the spa water 

CAN

 be cooled as well as heated. 

Lowering the set temperature point will ensure the heat pump engages/disengages a 
cooling cycle (if required) to maintain the desired set water temperature.   

 

 

If the spa control has been in standby mode (idle) for some time and the set temperature 
point is adjusted, the filtration/circulation pump may run for up to ten (

10

) minutes 

before 

the heater / heat pump engages to heat or cool (heat pump only) the water.   

Summary of Contents for SV2

Page 1: ......

Page 2: ...djusting Set Temperature Point 11 Heater Operating Mode 12 Heating Control Protection 13 Pump Operation 14 Air Blower Operation 15 Light Operation SV2 T models 16 Light Operation SV3 T SV4 T models 17 Sanitise Cycles 18 Special Function Buttons 19 Keylock 20 ADVANCED CONFIGURATION SETTINGS Setup Menu 21 Sleep Timers SNZE 24 Power Save Setting P SAV 25 Error Codes Troubleshooting 26 Heat Pump Error...

Page 3: ... to this appliance Read and follow all wiring instructions when connecting to power supply Any damaged cable must be replaced immediately To prevent electric shock hazard and or water damage to this appliance all unused receptacles must have a water proof seal in place Parts incorporating electrical components must be located or fixed so that they cannot fall into the bath or spa Parts containing ...

Page 4: ...MAINTENANCE It is your responsibility to regularly check and maintain the chemical water balance of the spa pool to ensure it remains within reasonable pH acid alkaline limits 7 4 7 6 pH Unbalanced water chemistry greatly accelerates corrosion and may lead to early product or component failure Product or component failures caused as a result of poor water chemistry maintenance will NOT be covered ...

Page 5: ...rgy efficient heat pump to the spa heating cooling contr0l system The SV heat pump interface revolutionises spa temperature control We can now offer both automatic heating and cooling of the spa water from 10 C 40 C all conveniently controlled via the spa side keypad whilst also providing greatly reduced heat recovery times which can be further reduced with the exclusive SV element boost and fast ...

Page 6: ...isplay modes DOWN BUTTON Short single presses toggle through the three display modes W TMP Water Temperature S TMP Set Temperature TIME Clock Holding the button will force the controller to begin adjusting the set temperature and will lower the set temperature point Also used for adjusting settings LIGHT BUTTON Press to toggle spa lights on off When light is first turned on the user has the abilit...

Page 7: ...y modes W TMP Water Temperature S TMP Set Temperature TIME Clock Holding the button will force the controller to begin adjusting the set temperature and will lower the set temperature point Also used for adjusting settings SANITISE BUTTON Press once to activate a 20 minute sanitisation and clean up cycle to refresh water quality after spa use A second press will cancel the cycle if already running...

Page 8: ...itisation and clean up cycle to refresh water quality after spa use A second press will cancel the cycle if already running BLOWER BUTTON Press to toggle blower on off A single press turns blower on in vari speed mode Use up down buttons to vary speed A double press activates the ramping mode PUMP A B C D BUTTONS Used to toggle the filtration pump and or any additional jet pump s on off if fitted ...

Page 9: ...ontroller will initiate a water priming sequence on start up During a priming sequence the filtration pump will run for up to 20 seconds at a time in an attempt to purge air from the plumbing The keypad display will scroll PRIMING during this sequence If the spa controller is successful in clearing all of the air from the heater tube the system will begin normal operation However if air is still d...

Page 10: ...Mode Icon Description W TMP Water Temperature S TMP Set Temperature TIME Clock Time Day The default display mode for all SV controller models is W TMP Water Temperature A short single press of the or button will navigate through the different display modes refer illustrations aside The purpose of the different display modes is to allow easy set temperature point and clock adjustment on all SV2 SV3...

Page 11: ...mode to TIME Press to enter clock adjustment The settings appear in the following order DATE Year yyyy Month mm Day dd Weekday mon sun TIME Format 24 hr 12 hr Hours xx 00 Minutes 00 xx Press the or button to set year month day hours and minutes to change between 24 hour format and 12 hour format Press the button to save each setting and move to the next setting IMPORTANT NOTES Leap years are taken...

Page 12: ...ime at differing times of day The advanced software constantly monitors and recalculates after each heating filtration cycle to ensure the correct daily filtration time is achieved and desired set water temperature is maintained Unless adjusted the SV controller will automatically heat to and maintain the default temperature of 38 o C The water temperature set point can be adjusted from 10 o C to ...

Page 13: ...roll AWAY MODE every 60 secs WEEK Week Monday to Thursday Demand heating is DISABLED and filtration fixed at 1 hour per day Friday to Sunday Normal Operation Press and hold and buttons together until MODE is displayed Press button to enter operating mode MODE adjustment Press or to select desired operating mode Press button to confirm and save setting IMPORTANT NOTES The Week mode is ideal for spa...

Page 14: ...ter and heat pump if fitted will operate however heater load shedding may occur when accessory pumps are running depending on controller settings At the end of each 10 minute WARM cycle the water temperature is checked If it is above 4 o C freeze protection stops and the controller returns to its prior state If the temperature is not above 4 o C another cycle will run Note Freeze protection overri...

Page 15: ...intention is to make best possible use of these buttons for all possible pump configurations For every press of a pump button the display will temporarily show the selected pump state ON OFF LOW HIGH AUTO and then revert to the default display mode The most common pump configurations and button assignments are referenced in the table aside IMPORTANT NOTES In configurations where a pump button cont...

Page 16: ...ode then present b SPD blower speed adjustment menu refer illustration aside Press or buttons to increase or decrease the blower speed note bar graph segments adjust with blower speed Press button to exit menu or wait for 10 second display time out Press button a second time to turn blower off Ramping Mode In this mode the blower speed gradually increases and decreases through the blower speed ran...

Page 17: ...f When light is turned on keypad will display light mode menu showing current light mode in use refer illustration aside Press or button to navigate through choice of light modes WHTE White Light UCLR User Colour FADE Fade Effect STEP Step Effect Press button to confirm light mode selection Dependant on light mode selected the keypad will display one of three light mode option screens refer aside ...

Page 18: ...to access light mode menu When light is turned on keypad will display light mode menu showing current light mode in use refer illustration aside Press or button to navigate through choice of light modes WHTE White Light UCLR User Colour FADE Fade Effect STEP Step Effect PRTY Party Effect Press button to confirm light mode selection Press to access light speed colour menu Dependant on light mode se...

Page 19: ...ise cycle Press button again to cancel cycle if desired IMPORTANT NOTES When the cycle is started automatic mode is enabled and if running any additional jet pumps and the blower are turned off If the controller falls within a designated sleep or power save period during a sanitise cycle the controller will not sleep until the sanitise cycle is finished Automatic Daily Sanitise Cycle The controlle...

Page 20: ...e Day display modes SV3 SV4 Models Invert Display On SV3 and SV4 model controllers the orientation of the keypad display can be inverted flipped 180 o for easy reading in and out of the spa Press button to invert display orientation IMPORTANT NOTES The operation of the and buttons also reverse to match the current display orientation If the display is left in the inverted orientation the display w...

Page 21: ...esent There are two types of keylock Full Lock all buttons are disabled Partial Lock allows use of pumps blower light and sanitise buttons however prevents adjustment of set temperature and other programmable settings Full Lock Press and hold until LOCK appears on the display Once locked if any button is pressed the key stroke will be ignored and display will show LOCK refer aside To unlock keypad...

Page 22: ...o adjust setting Press to confirm setting and exit menu Menu Item Setting Notes MODE Operating Mode Normal Economy Away Week Modes FILT Hours of filtration per day 1 to 24 hours F CYC Filtration cycle blocks Set filtration to run every 1 2 3 4 6 8 12 or 24 hrs SNZE Sleep time menu 1 SNZ Sleep timer 1 1 DAY Days of week 1 BGN Begin Time 1 END End Time 2 SNZ Sleep timer 2 2 DAY Days of week 2 BGN Be...

Page 23: ...pump type as follows Small circ pump Jet pump 2A or less 2spd or 1spd Minimum filtration hrs p day 1 1 Maximum filtration hrs p day 24 8 Default filtration hrs p day 4 3 F CYC Filtration Cycle Blocks how often filtration cycles occur This setting allows the user to adjust the frequency of the filtration cycle s The user can set filtration blocks to occur every hour right down to once a day or some...

Page 24: ...p mode of operation The H PMP setting choices are AUTO Heat pump will heat and cool Default HEAT Heat pump will only heat COOL Heat pump will only cool SV element heating also disabled OFF Heat pump disabled H ELE Heat Pump with SV Element Boost This setting defines how the in built SV electric heating element operates with a heat pump if fitted Set to OFF to disable electric heating Set to ON to ...

Page 25: ...erated by manual use without the need to adjust sleep time settings There are two individual sleep timers that can be set each of which can operate on one or more specified weekdays This enables the user to program different sleep times for different days ie weekdays vs weekends as well as custom settings on a particular day time where the user may want the spa silenced Press and hold and buttons ...

Page 26: ...s button to enter power save P SAV adjustment The power save setting consists of a choice of mode peak power period start time and peak power period end time refer table below Item Description Notes P SAV Power Save Mode Functions disabled during peak power periods OFF P SAV disabled default LOW Filtration disabled HIGH Filtration Heating disabled BGN Begin Time Peak power period begins Adjustable...

Page 27: ...ecking the heartbeat LED on the front of the spa pack itself ER 2 HEATER PLUG Problem No heater sensor communication Cause Internal heater sensor communication problem Solutions Turn mains power OFF wait 5 minutes then restart spa Contact spa reseller if problem is not resolved with power reset ER 3 WATER PRIME Problem Water prime failed air detected in heater tube Cause Airlock in pipe work low w...

Page 28: ...d Systematically unplug lights in pool temp sensor keypads and expansion port loads from spa pack one by one to identify faulty part Contact your spa reseller if problem persists ER 8 CTRL FAULT HVS Problem Heater relay is on when it should be off Cause Power surge periods of low or high voltage water on spa pack terminal block relay problem Solutions Turn mains power OFF and back ON again to see ...

Page 29: ...eat exchanger thermal cut out open IMPORTANT NOTE If a heat pump encounters an error the heat pump will remain disabled until the mains power to the SV spa controller is turned OFF and back ON again The heat pump warning message will continue to scroll every 60 seconds until the power is reset Maintenance Timers SERVICE REMINDER MESSAGES Certain spa manufacturers will choose to take advantage of t...

Page 30: ...Details Spa Net Pty Ltd Unit 4 103 Railway Road North Mulgrave NSW 2756 Australia Phone 61 2 4587 7766 Fax 61 2 4587 8766 www spanet com au Technical Support Service service spanet com au Accounts Department accounts spanet com au Sales Department sales spanet com au ...

Reviews: