4. Installation Notice                                                                                               

 

Drawing 1 

 

 

 

 

 

 

 

 

     

 

 

 

 

 

Drawing 2 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Separate installation

Reader

Lock

Lock

In the same pipe

Reader

 

 

 

AR-721HV3 / 1356 

RS-232: The distance between PC and converter 

(AR-801CM) can not be more than 2 meters 

RS-485: The distance between converter (AR-801CM) and   

the farthest controller (or reader) can not be more than 300 meters. 

Wiegand: The distance between RS-485 reader (or controller)   

and Wiegand reader can not be more than within 3 to 5 meters. 

Do not run AC power in the same pipe with communication wire(See drawing 2).   

It should be separate installation (See drawing 1). 

AR-721H locate inside the secure area for use as an exit   

controller, the auxiliary reader locate exterior wall for use   

as an entrance reader, but not directly behind AR-721H.   

For best reading distance, offset the AR-721H and auxiliary   

reader by about 50 cm above and 12 m below (suggestion value). 

Normally, AR-721H will read a Card / Key Tag at up to 15   

cm. However, when AR-721H or optional auxiliary reader is   

mounted directly on a metal surface, the reading distance   

decreases slightly. To reduce this effect, install wood or   

plastic between the mounting surface and mounting plate,   

this will restore most of the reading distance. 

 

 

AR-721HV3 / 1356 

Exit Switch input must be a dry contact, with no voltage present. 

AR-721H can cover standard electrical boxes. 

AR-721H does not supply power to operate electric strike or magnetic locks – a 

separate supply is required. Refer to strike/magnetic lock manufactures instructions. 

If common power supply is used for both the AR-721H and electronic door lock, be 

sure to install the diode which is provided with the AR-721H. 

10  Alternatively, you can use any good 9-18 VDC supply that   

provides at least 150mA. DC power should be clean and filtered   

with no more than 1 VAC ripple (Peak to Peak). Do not run AC 

power in the same cable with DC power to the AR-721H. While 

it is always preferable to use a separate power supply for the   

AR-721H and strike. 

11  Run the following cables to the AR-721H location. Conduit is recommended to 

reduce the effects of EMI/RFI and for physical protection of the wires. 

 

 

We suggest that the customer use ”

Shield Twisted Pair” and   

avoid Star wiring f

or good communication when installation. 

 

a. 

We suggest using the following cable in RS-485 communication.

 

b. 

Please use the following installation method, it is correct. 

 

 

 

 

 

 

 

 

 

c. Don’t use the following installation method, it will cause   

communication error. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

801CM
   OR
Controller

Controller
   OR
Reader

 

801CM
   OR
Controller

Controller
   OR
Reader

 

The Difference of Cables 

 

Cable Types and Distances 

Wire Application 

Cable Type 

Description 

From Power Supply 

2-cond, 18-22 AWG 

n/a 

From Locking Device and power 

supply or gate operator 

2-cond. See Mfr’s Specifications n/a 

From external alarm system’s Door 

Monitor Switch (for shunting) 

2-cond, 18-22 AWG 

100 m 

From Exit Button   

2-cond, 18-22 AWG 

100 m 

From Optional Auxiliary Reader 

2-cond unshielded 22 AWG,   

plus a separate 4-cond,   

shielded 22-24 AWG cable 

50 cm - 12 m 

 
 
 
 
5. Front Panel Indicators                                                                                        
 

1.  In the programming mode, if no key or card entry is made within 30 seconds, it will 

automatically exit the programming mode. 

2.  In the programming mode, LED light green and flash rapidly. It means that the 

controller waits for entering. LED is red and flash rapidly, it means that the reader is 

busy. 

3.  LED light green and one beep sound mean acknowledge, LED light red and two 

beep sounds mean not acknowledge. 

4.  In card learn mode, after flash card, a green light and five beeps mean that same 

card have existed in controller. 

5.  In anti-pass-back access mode, five beep sounds mean violates 

access function. (For AR-721H4 and AR-721H8) 

6.  In arming state LED light green per 0.6 second. In disarming   

state LED light green per 1.5 second, In alarm state LED light red per 0.4 second. 

(For AR-721H4 and AR-721H8) 

7.  If three incorrect user code (or master code) are entered, keypad will be locked for 30 

seconds. 

8.  Press button

0

+

#

to luck/unlock keypad. 

9.  Press button

*

+

#

for all cards entrance allowance. 

10. Press button

#

to function as the Bell Output. 

Summary of Contents for AR-721HV3

Page 1: ...d 2 Features Calendar Time system supporting Providing proximity card flash edit mode for easy quick setting Two Sets of Auto Open Zone Function Built in opened door relay alarm relay and request to e...

Page 2: ...ate power supply for the AR 721H and strike 11 Run the following cables to the AR 721H location Conduit is recommended to reduce the effects of EMI RFI and for physical protection of the wires 6 We su...

Page 3: ...ver and setting 4 sets of Force code on PC Anyone of these 4 sets is workable User could press related code to turn on off its connected equipment diagram as below PC boad of Controller AR 716EV2 AR 7...

Page 4: ...in Blue Wiegand DAT 1 Input Wiegand 2 Thin Green Wiegand DAT 0 Input Beeper 3 Pink Beeper Output 5V 100mA Low 4 Brown LED Green Output 5V 20mA Max LED 5 Yellow LED Red Output 5V 20mA Max Table 3 Conne...

Page 5: ...rm system AR 721H Standalone Controller The installation of 721H Megnetic Door Contacts CN4 721H 7AC2 Magnetic Door Contacts NC Magnetic Door Contacts COM 12VDC 2A Power Supply RELAY Orange Door Senso...

Page 6: ...connecting disance between the 801cm and your pc can not be more than 2m CH1 Green Blue Blue Green CN1 SOYAL CN3 Blue Green 7AC2 CN2 CN4 721H RELAY SOYAL CN3 7AC2 CN2 CN4 721H Black Red CN2 CN3 RELAY...

Page 7: ...pping charges and to use the original shipping container or equivalent Customers shall seek assistance from the distributor who sold you product s Repaired or replaced product s are warranted for nine...

Page 8: ...beep means that the range of transponders user codes were deleted Step3 Press 30 Delete all Transponders Step1 Press and master code fallow an Step2 Enter 2 9 2 9 The LED flash red during 10 seconds...

Page 9: ...25 25th January 2000 Ex 235901 23 59 01 PM Step3 Press Other operation is same as AR 721H4 Easy Guide for example exit the programming mode change master code door relay release time delete one or man...

Page 10: ...llow White Purple Green Bule Black Red Output Selection AR 721H do anti pass back with 2 pcs of AR 661U Black Red Black Bule Green Purple White Yellow Red 38 When the distance between 2 pcs 661U is le...

Page 11: ...721HV3 series in this function Press 2 8 0 6 4 Open two doors This function is good for using together with auxiliary reader AR 721 HV3 and auxiliary reader open different door Note that this functio...

Reviews: