85
Setting
Description
off (default)
Each analog channel is sampled once and no filter is applied.
minimum of 3
Each analog channel is sampled three times per measurement cycle and the
minimum value is returned.
medium of 3
Each analog channel is sampled three times per measurement cycle and the
median value is returned.
mean of 3
Each analog channel is sampled three times per measurement cycle and the
mean value is returned.
J-I-H
AN3 (N) type
Measurement type of analog input channel
AN3
.
Setting
Description
voltage 2.5 (default)
Analog voltage input 0V … 2.5V.
NTC
Measures the resistance of an NTC-thermistor.
R meas > 2k
Measures a resistance >2 kΩ.
J-I-I
AN4 (D) type
Measurement type of analog input channel
AN4
.
Setting
Description
voltage 2.5 (default)
Analog voltage input 0V … 2.5V.
voltage 0.3
Analog voltage input 0V … 0.3V.
R meas > 1k2
Measures a resistance >1.2 kΩ.
R meas < 1k2
Measures a resistance <1.2 kΩ.
PT1000
Measures the resistance of a PT1000 temperature sensor.
J-J
Camera
Configuration of the RS-485 camera port.
A
Switch
off
B
Warm-up time
30
sec
C
Solar nightshutdown
on
D
View
J-J-A
Switch
Powering of a connected camera.
Setting
Description
off (default)
Camera is not powered by the MRL-7
1
Camera is connected to switched 12-V supply
SW1
.
2
Camera is connected to switched 12-V supply
SW2
.
3
Camera is connected to switched 12-V supply
SW3
.