10
5.1.
Installation requirements
The minimum distance between the free-standing pellet fire unit and particularly
flammable surfaces is specified in Figure 9. The top of the unit must be at least 100cm
separated from the ceiling, especially in rooms with ceilings consisting of flammable
materials. The base supporting the unit cannot be made of combustible material (e.g.,
carpet), so make sure you use an adequate protection.
a)
b)
Figure 9 - Minimum distances from all surfaces: a) upper view of the unit's installation; b) side view of the unit's
installation
WARNING!
Keep combustible and flammable materials at a safe distance.
5.2.
Installation of ducts and fume extraction systems
• The exhaust pipe must have been designed for this purpose, in compliance to the
location requirements and in accordance with any applicable regulations.
•
Important! An inspection-T with an airtight lid must be attached to the exhaust
pipe of the unit to allow the regular inspection of the system or discharge of heavy
dust and condensates.
• As indicated in Figure 9, the exhaust pipe must be assembled so as to allow cleaning
and maintenance of the pipe by inserting inspection points.
• Under normal operating conditions, the combustion gas flow should create a draught
of 12 Pa one meter above the chimney neck.
Summary of Contents for Hidro 12
Page 18: ...12 Figure 11 specifies the basic requirements for installing the chimney to the unit a b ...
Page 102: ...96 ...
Page 103: ...97 ...
Page 104: ...98 ...
Page 133: ...127 25 2 Flow chart Hidro 12 Flow chart 1 Lighting ...
Page 134: ...128 ...
Page 135: ...129 Flow chart 2 Disabling Note The circulator pump off below 40 C water temperature ...
Page 136: ...130 25 3 Flow chart Hidro 17 and Hidro 23 Flow chart 1 Lighting ...
Page 137: ...131 ...
Page 138: ...132 Flow chart 2 Disabling Note The circulator pump off below 40 C water temperature ...