10. Troubleshooting and Inverter Messages
Although the inverter is designed for many years of power production there may be instances
where error messages may are displayed on the LCD screen. This table can be used to help
identify the error and resolve it.
Type
Name
Definition
Possible causes
Recommended solutions
Alarm
1- TempSensorErr
Abnormal
temperature
reading
1- Internal temperature
sensor is making poor
contact
1- Verify temperature
reading off of the display
2- Switch off the inverters
internal disconnects
2-Temperature sensor is
damaged
3- Switch the Inverter
back on
4- If error does not clear,
contact Solectria
Customer Service
Alarm
2- SPICommErr
Inverters
internal
communication
failure
1-Poor connection of the
inverters internal
communication connector
1- Observe for 5 minutes
and see whether the
alarm is cleared
automatically
2- Switch off the inverters
internal disconnects
3-Switch the Inverter back
on
4-If error does not clear,
contact Solectria
Customer Service.
Alarm
3- IntFanErr
Inverters
internal fan
(can’t be seen
externally) is
not operating
properly
1-Fan service life has
expired
1- Observe for 5 minutes
and see whether the
alarm is cleared
automatically
2- Switch off the inverters
internal disconnects
2-Fan connector is making
a poor connection
3-Switch the Inverter back
on
4-If error does not clear,
contact Solectria
Customer Service.