Parameter Settings
29
29
29
29
Press Mode
Set Dip Switch # 1 to ON, to Advance to:
I/O PROGRAMMING
PARAMETERS
Press Select
Then press
keys to set Terminal # 7 function
Range: Test or Reset.
PROG. INPUT # 7
RESET
Press Select
Then press
keys to set Terminal # 8 function
Range: Dual Adjustments, Reset
PROG. INPUT # 8
DUAL ADJUSTMENT
Press Select
Then press
keys to set Fault Relay function
Range: Fault, Fault – Fail Safe
FAULT RELAY TYPE
FAULT
Press Select
Then press
keys to set Immediate Relay function
Range: Immediate, Shear-Pin
IMM / S.PIN RELAY
IMMEDIATE
Press Select
Then press
keys to set Imm / S. Pin Relay On
Delay.
Range: Immediate 0-60 sec. / Shear-Pin 0-5 sec.
RELAY ON DELAY
0 SEC.
Press Select
Then press
keys to set Imm / S. Pin Relay Off
Delay.
Range: Immediate 0-60 sec. / Shear-Pin 0-5 sec.
RELAY OFF DELAY
0 SEC.
Press Select
Then press
keys to set Normal or Inverted output.
Range: Normal, Inverted
ANALOG OUTPUT
NORMAL
Press Select
To store selected parameters, press
Store
key
STORE ENABLE
I / O PROG. PARAM.
When parameters are correctly stored the LCD displays
DATA SAVED OK
This concludes
I/O PARAMETER
setting.
Press Mode
Set Dip Switch # 1 to ON, to Advance to:
COMM. PARAMETERS
Communication is optional and operates only when
starter incorporates this feature.
Note: Hardware and software are installed in the
factory.
Note:
The last command determines the function
when using communication and local
commands.
Protocol is factory set to the correct one according
to installed hard
ware.
COMM. PROTOCOL
MODBUS
For PROFIBUS parameters see page 30.
Press Select
Then press
keys to set Communication Baud Rate.
Range: 1200-9600 BPS
BAUD RATE
9600
Press Select
Then press
keys to set Communication Parity
Check. Range: Even / Odd
PARITY CHECK
EVEN
Press Select
Then press
keys to set Communication Serial Link
Number
Range: 1-248 (for up to 32 starters on one twisted pair)
SERIAL LINK NO.
248 (OFF)
Note:
Serial link number must be set to 248 (Off) if
communication is not in use.
To store selected parameters press
Store
key
STORE ENABLE
COMM. PARAMETERS
When parameters have been correctly stored the LCD
displays:
DATA SAVED OK
This concludes
COMMUNICATION
PARAMETERS
setting.