g-1-4) Export control
This function enables the inverter to control energy exported to the grid. Factory
value is a default value, which can not be changed. User value is usually set by
installer, it must be a value smaller than the factory value.
Note: For 0 Feedin control, please set the user value to 0.
g-1-6) Hot standby setting
This function allows the inverter to stay standby. It can directly respond and work
when load power is detected without self-check.
The default value is “Enable”. Select ”Disable” means the function is turn off.
User value:
Export Control
4000W
Hot Standby Setting
Disable
>Function Control
g-1-8) Grid Service
Grid Service can be selected from “Sustain” or “Stop” . The default is “Sustain”.
The safety requirements of battery storage inverter in each country may be different.
User can select “Stop” to turn off these features if user receives legal permission.
“Sustain” means user switch on all option from safety and it is default setting.
Function Control
>Sustain<
Grid Service
g-1-7) Phase Power Balance
This function controls the distribution of AC output power.
“Enable” means each phase will be divided according to the loads connected with
each phase. “Disable”, set as default, means each phase power will be divided
equally.
Function Control
>Disable<
Phase Power Balance
2kw
3kw
4kw
If 9kw AC power can be exported, each phase power will
be divided as above according to different loads connected
with each phase.
meter
load1
2KW
load2
3KW
load3
4KW
three phase
inverter
3kw
3kw
3kw
If 9kw AC power can be exported, each phase power will
be divided equally as above and it is unrelated with the
loads connected with each phase.
meter
load1
2KW
load2
3KW
load3
4KW
three phase
inverter
enable mode
disable mode
W(Gra) (applies to NZS4777.2)
W(Gra) is Gradient of power rate limit which is required by standard NZS4777.2 and
applies to NZS4777.2 only. This function is defined as a percentage of rated power
per minute.
The default value is “enable”. Choose “disable” means the function is turned off.
>W(Gra)
Grid
16.67%
g-1-9) H/LVRT Function
When the grid appears unusual situation in a very short time, this function
can keep the inverter in a no-power and no-alarm situation in such short
period of time and recover to work immediately once the grid gets back to
normal. The effective time is 800ms by default, but it will vary from the
different safety code selected.
"Enable" means this function is turned on and it is the default setting.
"Disable" means such function is off.
Function Control:
H/LVRT Function
Enable
g-1-5) Remote control
This function allows external control device to make the inverters remote cluster
control through RS485 port on the inverter. And it can control the inverter’s active
power output and reactive power output.
The default value is “Disable”. If it can connect successfully, it will display
“Connected”. If not, it will display “Connecting”. Select ”Disable” means the function
is turn off.
Remote Control
Enable
Connecting...
>Function Control