Setting
Setting
64
65
g-1-11) DRM Function(applies to NZS4777.2)
DRM function is Demand Response Mode which is required by standard
NZS4777.2 and applies to NZS4777.2 only.
The default value is “enable”. Choose “disable” means the function is turned off.
>Function Control
DRM Function
Enable
g-1-12)Power Limit
Power limit function is able to set AC port maximum power by percentage.
>Proportion
Power Limit
1.00
Battery
Charger
EPS System
(g-2)
(g-2-1)
(g-2-2)
g-2-1) Charger
User can change the parameters of charger here. Battery type includes
Lithium and Lead-acid. Users can set the charge & discharge parameters
and awaken mode.
For the detailed parameters , please refer to the figures below.
>Min Capacity
10%
Charger
Charge Max
Charger
Current 35A
Discharge Max
Charger
Current 35A
>Battery Awaken
Charger
NO
For Lithium battery
For Lead-acid Battery
Charge Absorp
Voltage
Charger
Charge Float
Voltage
0.0V
Charger
0.0V
Discharge cut
Voltage
0.0V
Charger
Charge Max
Current
Charger
0.0A
Discharge Max
Current
Charger
0.0A
>Battery Type
Lithium
Charger
>Grid-tied Min Limit
Charger
>Function Control
Enable
Grid-tied Min set
>Min Capacity
10%
Grid-tied Min set
>Grid-tied Min Limit
Charger
>Function Control
DRM Function
Enable
g-1-10) PU Function(For specific country if required by the local grid)
PU function is volt-watt response mode which is requried by some specific
country standard such as AS4777.2. This function can control the inverter’s active
power according to grid voltage.
"Enable" means this function is turned on and it is the default setting.
"Disable" means such function is off.
PU Function
Enable
PU Function
220.0V
Response V2
PU Function
250.0V
Response V3
PU Function
265.0V
Response V4
>PuFunction