2. Safety

Safety

Safety

2.1 Important Safety Instructions

Danger!
Danger to life due to high voltage in the inverter!

All work  must be carried out by qualified electrician.
The appliance is not to be used by children or persons with                  
reduced physical sensory or mental capabilities, or lack of 
experience and knowledge, unless they have been given 
supervision or instruction.
Children should be supervised to ensure that they do not play 
with the appliance.

Caution

!

Danger of burn injuries due to hot enclosure parts!

During operation, the upper lid of the enclosure and the enclosure 
body may become hot.
 Only touch the lower enclosure lid during operation.

Caution

!

Possible damage to health as a result of the effects of radiation!

Do not stay closer than 20 cm to inverter for any length of time.

Warning

Authorized  service  personnel  must  disconnect  both  AC  power 
from  inverter  before  attempting  any  maintenance  or  cleaning  or 
working on any circuits connected to  inverter.

Do not operate the  inverter when the device is running.

Warning

 

!

Risk of electric shock!

Warning

 

!

Prior to the application, please read this section carefully to ensure correct and 
safe application. Please keep the user manual properly.
Accesories  only  together  with  the  inverter  shipment  are  recommanded  here. 
Otherwise may result in a risk of fire, electric shock, or injury to person.
Make  sure  that  existing  wiring  is  in  good  condition  and  that  wire  is  not 
undersized. 
Do not disassemble any parts of inverter which are not mentioned in installation 
guide.  It  contains  no  user-serviceable  parts.  See  Warranty  for  instructions  on 
obtaining service. Attempting to service the inverter yourself may result in a risk 
of electric shock or fire and will void your warranty. 
Keep away from flammable, explosive materials to avoid fire disaster.
The installation place should be away from humid or corrosive substance.
Authorized  service  personnel  must  use  insulated  tools  when  installing  or 
working with this equipment.
The unit contains capacitors that remain charged to a potentially lethal voltage 
after the MAINS and battery have been disconnected.
Hazardous voltage will present for up to 5 minutes after disconnection from 
power supply.
CAUTION-RISK of electric shock from energy stored in capacitor, Never operate 
on the inverter couplers, the MAINS cables or Battery cables when power is 
applied. After switching off the battery and Mains, always wait for 5 minutes to 
let the intermediate circuit capacitors discharge before disconnecting battery 
plugs and MAINS cables.
When accessing  the internal circuit of inverter, it is very important to wait 5 
minutes before operating the  power circuit or demounting the electrolyte 
capacitors inside the device. Do not open the device before hand since the 
capacitors

time to sufficiently discharge!

 require 

Measure the voltage between terminals UDC+ and UDC- with a multi-meter 
(impedance at least 1Mohm, voltage must be less than 35VDC) to ensure that 
the unit is discharged before starting to do any operation inside the device.

Lightning will cause a damage either from a direct strike or from surges due to a 
nearby strike.

Specialists in lightning protection should be consulted during the end use 
application.
Using appropriate external lightning protection, the effect of a direct lightning
strike into a building can be mitigated in a controlled way, and the lightning
current can be discharged into the ground.

Installation of SPDs to protect the inverter against mechanical damage and
excessive stress include a surge arrester in case of a building with external
lightning protection system (LPS) when separation distance is kept.

To protect the AC system, surge suppression devices (SPD type2) should be
fitted at the main incoming point of AC supply (at the consumer’s cutout), 
located between the inverter and the meter/distribution system; SPD (test
impulse D1) for signal line according to EN 61632-1.

04

05

Summary of Contents for X3-Fit-10.0-C

Page 1: ...this manual belongs to Solax Power Network Technology Zhe jiang Co Ltd Any corporation or individual should not plagiarize partitially or fully copy including software etc and no reproduction or distr...

Page 2: ...General Data 4 4 EPS output apply to version E only 4 3 Efficiency Safety and Protection apply to version E C 4 2 Internal Charger apply to version E C 4 1 AC output input apply to version E C 5 3 Mo...

Page 3: ...Note provides tips that are valuable for the optimal operation of our product Warning Warning indicates a hazardous situation which if not avoided could result in death or serious injury 03 8 Setting...

Page 4: ...rrosive substance Authorized service personnel must use insulated tools when installing or working with this equipment The unit contains capacitors that remain charged to a potentially lethal voltage...

Page 5: ...l be conducted by licensed electrician and shall comply with Australia National Wiring Rules Battery Safety Instructions SolaX X3 Retro Fit series inverter can only work with high voltage battery for...

Page 6: ...operating and servicing the unit If ignored physical injury or death may follow or damage may occur to the unit Read this instruction before you work on the unit If you are unable to understand the d...

Page 7: ...he inverter will stop with an overload fault warning Please confirm with the local grid supplied whether there is any special regulation for connecting to the grid Digram A applies to the wiring rules...

Page 8: ...redundant power will export to the public grid as set in Export Control The charging and discharging time can be set flexibly In the case of the external generator the power generated will be used to...

Page 9: ...10 0E X3 Fit 10 0C 8000 8000 11 6 12 8 10000 10000 14 5 16 0 10000 10000 14 5 16 0 400V 230VAC 380V 220VAC 50 60 8000 11 6 12 8 8000 11 6 12 8 10000 14 5 16 0 10000 14 5 16 0 400V 230VAC 380V 220VAC 4...

Page 10: ...l Transformerless RS485 Meter WiFi optional DRM USB ISO alarm Backlight 20 4 character 10 years optional Standard 5 years Max Battery charge discharge efficiency 96 00 96 50 4 4 EPS output apply to ve...

Page 11: ...ent temperature in the range of 20 to 60 The slope of the wall should be within 5 The wall for mounting the inverter should meet conditions below 1 Solid brick concrete or strength equivalent mounting...

Page 12: ...rter 1 3 Hammer the expansion tubes in the holes and tighten them Then install the wall bracket with the expansion screws The screwdriver Torque 4 5 0 2Nm Installation tools crimping pliers for bindin...

Page 13: ...a 3 3 Remove 12mm of insulation from the end of wire 3 4 Insert stripped wires into AC terminal and insure all conductor strands are captured in the AC terminal 3 5 Crimp the AC terminal head by using...

Page 14: ...de above espescially for the wiring of neutral line grounding and RCD please contact us before any operation Electrical Connection Electrical Connection 24 25 EPS wiring diagram The below diagram are...

Page 15: ...ut power When an over load occurs please adjust the EPS loads to make sure it is within the EPS output power range then turn the inverter back on For the nonlinear load please make sure the inrush pow...

Page 16: ...se ensure that all the inverters software version must be the same otherwise the parallel function will not work Step1 Connect all inverters communication together by connecting network cables between...

Page 17: ...l of all slaver inverters energy management and distribution control Once the master inverter comes with an error and stop working all the slavers will stop simultaneously But the master can work inde...

Page 18: ...erter and battery is CAN with a RJ45 connector BMS PIN Definition Note The battery communication can only work when the battery BMS is compatible with the inverter Step4 Tighten the screw connectors T...

Page 19: ...ath and insert the commu nication cable through the cable nut Electrical Connection Electrical Connection 36 37 Meter is used for monitoring the power usage for entire house at the meantime inverter w...

Page 20: ...t the communication terminal into the BMS port Step1 Disassemble the BMS cable gland Step2 Prepare a communication cable without sheath and insert the commu nication cable through the cable nut Step1...

Page 21: ...IN definition and port position will be slightly different COM Port COM DRM is provided to support several demand response modes by emitting control signals as below DRM1 5 DRM2 6 DRM3 7 DRM4 8 3 3V D...

Page 22: ...er manual Pocket GPRS user manual for more details 6 9 LAN Connection LAN communication is the standard communication interface It can transmit the data between the router and inverter via the local n...

Page 23: ...are commissioned in Italy The Italian standard requires that all inverters feeding into the utility grid are equipped with a self test function in accordance with CEI 0 21 During the self test the in...

Page 24: ...SP respectively It will be like Update ARM 618 00098 00_Hybrid_X3G3_Manager_VX XX_XX XX usb Update DSP 618 00096 00_Hybrid_G3X3_Master_VX XX_XX XX hex VX XX is version number xx xx is le compilation d...

Page 25: ...s Off The inverter is in fault status Constant green The battery communication is working Flashing green The battery communication is normal and in idle status Off The battery does not communicate wit...

Page 26: ...lease refer to the inverter for the most updated structure Inverter DSP2 Self Test Charger setting Inv Warning Reset Inv Energy Factory Reset 49 Hot Standby Settings Power Limit BAT M SN BAT PS1 SN BA...

Page 27: ...is plugged with a smart plug this status shows the real time load power include load1 power and load 2 power L1 Power 0W Load b Charger This status shows the charger situation of the system including...

Page 28: ...EPS Yield b EPS Yield The EPS Yield function contains charger yield for today and total Inverter Yield EPS Yield Load Consume History Inv Warning Load 1 consume Load 2 consume Load consume c Load cons...

Page 29: ...ssword to operate most of the professional settings The installer password is 2014 Date Time Language Ethernet Setting b Language This inverter provides several languages for customer to select a Date...

Page 30: ...Mode Charge Start time 2 08 00 Work Mode Charge End time 2 08 00 Work Mode Setting Setting 56 57 e Relay Control Relay Control is a reserved function which can control designated load intelligently b...

Page 31: ...notice Item 7 1 2 3 4 5 6 Country VDE 0126 ARN 4105 German AS 4777 Australia G98 2 UK EN 50438_NL Netherland CEI 0 21 Italy IEC61727_In India Standard German g 1 2 Power Factor For specific country if...

Page 32: ...EN50438_NL only OFPL_StartPoint FreqDropRate Frequency droop rate Under Frequency power limit start point Over Frequency power limit start point UFPL_StartPoint OFPL_StartPoint Apply to EN50438_DK on...

Page 33: ...according to different loads connected with each phase meter load1 2KW load2 3KW load3 4KW three phase inverter 3kw 3kw 3kw If 9kw AC power can be exported each phase power will be divided equally as...

Page 34: ...Charger Current 35A Battery Awaken Charger NO For Lithium battery For Lead acid Battery Charge Absorp Voltage Charger Charge Float Voltage 0 0V Charger 0 0V Discharge cut Voltage 0 0V Charger Charge M...

Page 35: ...EPS output is overloaded Frequency can be set to 50 or 60Hz based on your load loads EPS auto restart is used for restarting EPS output power manually or automatically Choose disable means the EPS out...

Page 36: ...eter Setting X3 Retro Fit inverter with Energy meter connected can achieve hybrid functions You can disable the meter function then it can work as a normal grid tied inverter without PV and meter conn...

Page 37: ...and pocket GPRS Register2 SN it indicates the serial number of built in Ethernet About This interface shows basic information of the inverter including inverter serial number Register1 serial number R...

Page 38: ...seek help from installer 72 73 Troubleshooting AC10M Volt Fault The grid voltage is out of range for the last 10 Minutes The system will back to normal if the grid is back Or seek help from installer...

Page 39: ...can not go back to normal state 74 75 Troubleshooting BMS_External_Err Battery Fault external fault Please contact battery suppiler BMS_Internal_Err Battery Fault internal fault Please contact battery...

Page 40: ...ease contact the installer or SolaX to arrange qualified person who has adequate training knowledge and practical experience to perform these tests Please kindly noted this action is not covered by wa...

Reviews: