6. Troubleshooting
34
35
6
Troubleshooting
6.1
Troubleshooting
Check the indicators on the front to determine the state of the T-BAT system. A
warning state is triggered when a condition, such as with voltage or temperature,
is beyond design limitations. The T-BAT system's BMS periodically reports its
operating state to the inverter.
When the T-BAT system falls outside prescribed limits, it enters a warning state.
When a warning is reported, the inverter immediately stops operation.
Use the monitoring software on the inverter to identify what caused the warning.
The possible warning messages are as follows:
BMS_External_Err
The communication
between BMS and
Inverter is interrupted
Check if the
communication cable
between BMS and Inverter
is correctly and well
connected.
BMS_Internal_Err
1. DIP switch at the
wrong position;
2. The communication
between battery
modules is interrupted
1. Move the DIP switch to
the correct position;
2. Check if the
communication cable
between battery modules is
correctly and well
connected.
BMS_OverVoltage
Battery over voltage
Please contact SolaX after-
sales service or your
distributor directly.
BMS_LowerVoltage
Battery under voltage
Please contact SolaX after-
sales service or your
distributor directly.
BMS_ChargeOCP
Battery charge over
current protection
Please contact SolaX after-
sales service or your
distributor directly.
BMS_DishargeOCP
Battery discharge over
current protection
Please contact SolaX after-
sales service or your
distributor directly.
Warning Messages
Description
Troubleshooting
6. Troubleshooting
BMS_TemHigh
Battery over
temperature
Wait till the temperature of cells go
back to the normal state.
BMS_TemLow
Battery under
temperature
Wait till the temperature of cells go
back to the normal state.
BMS_CellImblance
The capacities of
cells are different
Please contact SolaX after-sales
service or your distributor directly.
BMS_Hardware_Protect
Battery hardware
under protection
Please contact SolaX after-sales
service or your distributor directly.
BMS_Insulation_Fault
Battery insulation
fault
Please contact SolaX after-sales
service or your distributor directly.
BMS_VoltSensor_Fault
Battery voltage
sensor fault
Please contact SolaX after-sales
service or your distributor directly.
BMS_TempSensor_Fault
Battery
temperature
sensor fault
Please contact SolaX after-sales
service or your distributor directly.
BMS_CurrSensor_Fault
Battery current
sensor fault
Please contact SolaX after-sales
service or your distributor directly.
BMS_Relay_Fault
Battery relay fault
1. Make sure the power cable is
correctly and well connected to
the power connector (XPLUG) of
the BMS;
2. If the rst step still does not
work, please contact SolaX after-
sales service or your distributor
directly.
BMS_Type_Unmatch
The type of BMS
unmatched
Please contact SolaX after-sales
service or your distributor directly.
BMS_Ver_Unmatch
The version of
BMS unmatched
Please contact SolaX after-sales
service or your distributor directly.
Warning Messages
Description
Troubleshooting