4. Installation
4. Installation
24
25
4.5.3
Connecting CAN Communication Cable
It is required for the BMS to communicate with the inverter for proper operation.
3. Plug the other end of the CAN
communication cable to the CAN connector on
BMS. Tighten the screw cap at the end of the
cable.
2. There's a protect cap for the CAN connector
on BMS, unscrew the cap.
The wire order of the communication cable is the same as RS485
communication calbe
CAN
BAT
+
-
Sequence
1
2
3
4
5
6
7
8
CAN
GND
CAN_H CAN_L
A1
B1
1. Turn off the Inverter, insert one end of the
CAN communication cable (D) to the BMS port
on the Inverter. Assemble the cable gland and
tighten it.
4.5.4
Connecting Ground Wire
For one battery module:
Unscrew the ground terminal with hexagon wrench on BMS and battery module
at either side of the ground port as marked at the following figure. Connect the
ground wire from BMS to battery module.
Note: 10AWG ground wire is required for grounding.
CAUTION!
GND connection is mandatory!
For 2~4 battery modulles:
The GND connection between BMS and battery module is the same as
described above.
The terminal point for GND connection between battery modules are circled in
red bellow:
Left side of battery module
Right side of battery module