Additional system-specific load limits can be found in the download area
at www.solarwatt.com.
4
Under mechanical load, no contact between solar glass and hard materials (eg. metal,
glass) may occur. The drainage holes in the module frame must not be covered, as it could
cause frost damage on the module frame. Do not place any plug connectors in the frame.
NOTE
Electrical connection and grounding
SOLARWATT solar modules are equipped at
the factory with high-quality solar cables
and reverse-polarity protected, shock proof
plug connectors. The connection of the string
line has to be done with identical connec
-
tors manufacture and type as to the module
connecting cable. To be able to ensure this the
module connector at the beginning and the
end of the string may be removed and repla-
ced (More information in the download area at
www.solarwatt.com). The allowed cross-section
and outer-diameter of the cable and instruc-
tion of the manufacturer have to comply. The
SOLARWATT pricelist contains matching cable-
sets, plugs, cables and installation accessories.
When connecting the modules, ensure that
the plugs engage with an audible click. The
common bending radii of at least 5 times the
outer cable diameter must be complied with. It
is recommended to lay the cable firmly so that
they are not subjected to mechanical loads.
The cable and connector must not exposed
to moisture and will not rest on the ground or
floor.
Solar modules generate electrical energy on the front side during incidence of light. A
system with multiple solar modules can generate life-threatening voltages and electri-
cal currents. Do not touch the electrical connections or cable ends while the solar mo-
dule is exposed to light.
WARNING
To ensure safety and compliance with the
technical data of the products, only original
tools of the manufacturer may be used in the
self-assembly of solar cables.
Connection of modules in series is only per-
mitted up to the maximum system voltage as
listed in applicable data sheet. The maximum
number of solar modules installed parallel
without string fuse is two. Please comply
with the value specified in the data sheet for
reverse current feed and only use standardi-
zed photovoltaic cables (recommendation: at
SUBJECT TO CHANGE | © 2017 SOLARWATT GMBH | AZ-TM-PMS-0673 | REV 012 | STATUS: 08/2017 | PAGE 25