a. Mark the location of the bracket screw for the Connection Unit, and optionally
the two additional bracket holes.
Figure 9: Connection Unit bracket
b. Remove the inverter from the wall/ pole.
c. Drill the hole for the Connection Unit bracket.
d. Hang the inverter on the mounted brackets.
e. Fasten the Connection Unit bracket using a standard bolt.
7. Insert the screws at the top of the inverter brackets and fasten the brackets together.
8. Verify that all the brackets are firmly attached to the mounting surface.
Selecting a Residual Current Device (RCD)
IMPORTANT SAFETY FEATURE
All SolarEdge inverters incorporate a certified internal Residual Current Device
(RCD) in order to protect against possible electrocution and fire hazard in case
of a malfunction in the PV array, cables or inverter. There are two trip
thresholds for the RCD as required for certification (DIN VDE 0126-1-1). The
default value for electrocution protection is 30 mA, and for slow rising current
is 300 mA.
If an external RCD is required by local regulations, check which type of RCD is required
for the relevant electric code. Install the residual-current device (RCD) in accordance
with the applicable local standards and directives. SolarEdge recommends using a type-
A RCD. The recommended RCD value is 100 mA or 300 mA unless a lower value is
required by the specific local electric codes. When required by local regulations, the use
of an RCD type B is permitted.
NOTE
For multiple inverters, an RCD per inverter is required.
In installations where the local electric code requires an RCD with a lower leakage
setting, the discharge current might result in nuisance tripping of the external RCD. The
following steps are recommended to avoid nuisance tripping of the external RCD:
Single Phase Energy Hub Inverter MAN-01-00812-1.1
28
Selecting a Residual Current Device (RCD)