Troubleshooting
34
13.1 auto-Learning Battery Run Times
As
batteries age, the estimated run times may become less accurate. The S4K6U10000 is programmed to “learn”
from a full battery discharge and modify the estimated run time for the measured battery capacity. This can
improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
• The UPS must have a steady load that is greater than 20%.
• The UPS must be at 100% charge at the start of a battery discharge.
• The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the battery table
on the right will be restored. This will override any value that is automatically learned.