11.2 pin 4 - Remote Shutdown on Battery
1. T
his pin is functional only when the UPS is in battery mode. If the UPS is being powered by the utility, Pin 4 will
ignore any signal on this pin.
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes form the serial port using
Sola/Hevi-Duty’s contact closure cable. It cannot be used with just a contact closure unless the relay is used
to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or greater is required to signal a shutdown.
Signals for less than 1.5 seconds will be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds, the
command cannot be canceled.
3. A battery shutdown signal on Pin 4 will NOT cause an immediate Shutdown. A shutdown signal will start a
2-minute shutdown timer. The timer cannot be stopped. After 2 minutes, the UPS will shut down.
4. If the utility returns during the 2-minute timer countdown, the shutdown timer will continue until the end of 2
minutes and the UPS will turn OFF. The UPS must remain OFF for at least 10 seconds even if AC input power
Returns before the UPS turns OFF. This serves to reset and restart the server.
Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown delay.
11.3 UpS Intelligent Communications
The S4K6U10000 is equipped with an Intellislot® port to provide advanced communication and
monitoring options.
Sola/Hevi-Duty’s MultiLink software continually monitors the UPS and can shut down your computer or server in
the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP WEB CARD is
installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the network with
other computers running MultiLink when you purchase a MultiLink License Kit. For more information about the
Intellislot SNMP WEB CARD and MultiLink License Kits, visit our Web site (
www.solaheviduty.com
) or contact
your local distributor or Sola/Hevi-Duty representative.
Several option cards are available for use in the Intellislot port of the S4K6U10000. The Intellislot “
SNMp WEB
CaRD
” provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot “
Multiport4Card
” allows you to install MultiLink software on four computers and coordinate
shutdown in the event of a power failure.
The Intellislot “
Relay Card-Int
” provides dry contact relay outputs for custom wired applications and delivers
support for built-in shutdown for AS/400 systems.
Communications
CaUTION
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be
segregated and run separate from all other power cables, where applicable.
25
Summary of Contents for S4K6U10000
Page 1: ...S S4K6U10000 power availability On Line UPS 120 208V 120 240V USER MANUAL...
Page 2: ......
Page 46: ......
Page 47: ......