Figure 8 Control and indicator overlays, vertical and horizontal
Horizontal overlay for rack mounting
Vertical overlay
for tower
installation
All indicators lit for illustrative purposes.
S4K Industrial UPS
!
L1 L2
AC INPUT
- +
BATTERY
UPS ON
BYPASS
S4K Industrial UPS
!
- +
AC INPUT BATTERY UPS ON
BYPASS
L1
L2
Controls and indicators
9.0 c
ontrolS
and
i
ndicatorS
9.1 ON/alarm Silence/Battery Test Button
This button controls output power to connected load(s) and has three functions:
• ON
• Alarm Silence
• Manual Battery Test
ON
- Pressing this button will startup the UPS in order to provide conditioned and
protected power.
alarm Silence
- To silence alarms, press this button for at least one Second. After the alarm is
silenced, the S4K6U10000 will reactivate the alarm system to alert of additional problems.
9.2 OFF/Bypass Button
This button controls output power to connected load(s) and has dual functions:OFF and Bypass.
Manual Battery Test
- To initiate a manual battery test, press the ON/Alarm Silence/Battery Test button for at
least one second while operating from utility power with no alarm conditions present.
• If only three of the five Battery indicators illuminate, allow the UPS to recharge the batteries for 24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery indicators illuminate, contact your local
distributor, Sola/Hevi-Duty representative or Sola/Hevi-Duty Technical Support Group.
NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.
CaUTION
Pressing the OFF/Bypass button once will cause the load to be transferred
to bypass power. Once in Bypass pressing the OFF/Bypass button two
times within 4 seconds will turn the UPS off. This will result in a loss of power
to the receptacles and connected loads, but the UPS’s circuits remain live,
charging the units battery. Perform all necessary shutdown procedures on
connected loads before pressing this button.