EVERGEN M SERIES USER MANUAL
ASSEMBLy
14
by carmanah
®
6. Connect Solar Panel and fixture Cables to the EMS
1
Route the two (2) unconnected solar panel cables into battery box with enough slack to easily connect to
the EMS.
2
Route the end of the fi xture cable that has a two (2) position connector and ring terminal into the battery box
with enough slack to easily connect to the EMS. For systems with two fi xtures, repeat for the second fi xture
cable while using the fi xture splitter adapter.
3
Take the ground wire from the EMS and place it onto the grounding lug followed by the ground wire from the
fi xture cable.
4
Thread supplied 1/4"-20 nut onto ground lug grease and tighten to 5 ft-lbs (64 in-lbs).
GROUND
EMS
GROUND
WIRE
FIXTURE
2-POSITION
CONNECTOR
GROUND
WIRE
!GREASE!