28
© Softing Industrial Automation GmbH
dataFEED Gateway - User Manual
5.2.2 Siemens S7-2 Settings
In the
Siemens Settings
view you can configure the IP address of a S7-1200 or S7-1500 series PLC.
Note
This description only applies to the
uaGate SI
product!
The following settings are available:
Machine Access
Connection Name
Connection name to be used
Special characters are not supported.
IPv4 Address
IPv4 address of the PLC to which a connection should be established
Saving and applying settings
1.
Click the
Save
button to save your settings.
A hint will appear reminding you that the application of some other settings is pending:
2.
Click at this link. Your settings will be applied.
Depending on the number of modified settings this process may take some time before being completed.
3.
A message in the upper window part will inform you about the successful modification(s).
5.2.2.1
Filtering the Address Space of a Siemens PLC with Optimized Blocks
Note
This description only applies to the
uaGate SI
product!
Without filtering the complete available address space of a S7-1200/S7-1500 PLC with optimized blocks is
available for the OPC UA and MQTT data exchange using
uaGate SI
. However it is possible to filter the address
space thus to restrict the visible variables.
For doing so select the previously established connection to a S7-1200/S7-1500 PLC with optimized blocks and
click the
Symbol Import
button. In a next step it is possible to flip open the complete available address space in
the
Address Space
view and to select the individual variables to be accessed via OPC UA and MQTT respectively
to de-select these again.
If a specific variable in the controller's address space is selected its
Node ID
,
Node Class
,
Browse Name
,
Display
Name
and
Description
is shown in the
Properties
view
If full access to the whole PLC address space should be provided, then it is recommended to delete any filter
settings in advance.
Saving and applying settings
1.
Click the
Save
button to save and apply your settings.