BC-600-PB
Specifications
Softing
Page 41
13 Specifications
Power supply
Via external AC adapter 100 V .. 240 VAC 50/60 Hz (galvanically
isolated) or direct connection to 24 VDC ±20%, approx. 0.5 A
(without galvanic isolation)
RS485 (DP)
PROFIBUS D-sub connector (female), 9-pin,
switchable power supply for ext. bus termination
Protocol and frame analysis:
PROFIBUS DP and DPV1,
automatic baud rate detection 9.6 kbit/s .. 12 Mbit/s
Signal analysis:
PROFIBUS DP, DPV1, FMS and MPI;
signal quality index 0 .. 5000 determined from signal waveform
as well as signal/noise ratio and rise time;
signal sampling with 8/16 samples per bit
Oscillogram display:
Test range ±5V at 10mV resolution (differential), 0V…15V at
15mV resolution (A or B to DGND)
sampling rate: up to 384 MSamples/s,
for signal details: 2,400 sampled points,
for oscillogram analysis: 8,192 sampled points
Topology scan:
Active, maximum distance 230 m, accuracy ±2 m
USB
V 2.0, high speed 480 Mbit/s, galvanically isolated
Trigger
IN : L=0 .. 0.8 V; H=2.4 .. 24 V; pulse > 10
μs, active high
OUT: approx. 5 V, active low (connection to storage oscilloscope)
Internal memory capacity
10 memory locations for Quick Tests,
1 Trend log, max. 41 days
Dimensions
HxWxD: 35 x 170 x 110 mm
Weight
Test tool without cable: approx. 0.45 kg,
complete with carrying case, without accessories: approx. 3.9 kg
Protection class
IP 20
Permissible ambient
conditions
Operating temperature 0 .. 50 °C
Storage temperature -20 .. 70 °C,
Air humidity 10 .. 90% without condensation
Conformity
CE, FCC, VCCI
Operation
Via four-line display and four function keys or via PC/notebook.
Localization of the display: DE+EN+FR+IT+PL+ES
(without national specific characters)
PC operating software
PROFIBUS Diagnostic Suite, see separate manual