OPERATION OF THE DEVICE
100
HYD 5K...20KTL-3PH
3. Safety Parameters
Sets the country and grid code
4. Energy Storage Mode
Select between Self-use mode
(Standard), time-of-use mode, timing
mode, passive mode. See “Storage
Modes” chapter for details.
5. Auto-Test
(only for Italy)
6. Input Channel
Configuration
With the Input Channel Configuration
you define if PV and / or batteries are
connected and in what configuration. If
one of the Input Channels
Input Channel 1
(MPPT1)
if PV strings are connected to MPPT1,
select “MPPT1”
Input Channel 2
(MPPT2)
if PV strings are connected to MPPT2
independently, select “MPPT2”
If PV strings are connected to MPPT2
in parallel to MPPT1, select “MPPT1”
Input Channel 3 (BAT1) If a battery is connected to BAT1 input,
select “BAT1”, otherwise “disable”
Input Channel 4 (BAT2) if a second battery is connected to
BAT2 independently, select “BAT2”
If one battery is connected in parallel
to BAT1 and BAT2, select “BAT1”
7. EPS Mode
Enable / Disable the emergency power
supply mode (EPS). It is only available
if a battery is connected
8. Modbus address
Enter the Modbus address (when
several inverters require simultaneous
monitoring), standard: 01