ID28
DciOCP
The Dci is too high
Check the input mode (parallel mode/
independent mode) setting of inverter according
to Section 6.3 (C) 6.Input Mode of this user
manual, If it’s incorrect, change it according to
Section 6.3 (A)
ID29
SwOCPInstan
The grid current is
too high
Internal faults of inverter, turn OFF the “DC
switch”, wait for 5 minutes, then turn ON the
“DC switch”. Check whether the fault is
rectified. If no, please contact technical support.
ID30
SwBOCPInstant The input current is
too high
Check whether the input current is higher
than the maximum input current of inverters,
then check the input wiring, if both are correct,
please contact technical support.
ID33
Overload
Reflux overload
time out
Check if the load power is out of range, and
if so, adjust the power to the correct range.
ID49 ConsistentFault_
VGrid
The grid voltage
sampling value
between the master
DSP and slave DSP
is not consistent
ID49-ID55 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check whether
the fault is rectified. If no, please contact
technical support.
ID50 ConsistentFault_
FGrid
The grid frequency
sampling value
between the master
DSP and slave DSP
is not consistent
ID51 ConsistentFault_
DCI
The DCI sampling
value between the
master DSP and
slave DSP is not
consistent
ID52 ConsistentFault_
GFCI
The GFCI sampling
value between the
master DSP and
slave DSP is not
consistent
ID53
SpiCommLose
The spi
communication
between the master
DSP and slave DSP
is fault
ID54
SciCommLose
The Sci
communication
between the control
board
communication
board is fault
ID55
RelayTestFail
The relays fault
ID56
PvIsoFault
The insulation
resistance is too low
Check the insulation resistance between the
PV array and earth(ground), if a short circuit
occurs, rectify the fault.
ID57 OverTempFault_ The inverter temp is
Ensure the installation position and