NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
60
EN
General
Setup Item
Selectable Value
Default Value
Language
English/
简体中文/ 繁體中文/….
English
Audible Alarm
Enable/ Disable
Enable
LCD Back Light
Always On/ Auto Off
Auto off
Date
YYYY/MM/DD
Time
HH:MM:SS
Power Share Output
The Power Share Output can be set by LocalView sofware. For more details,
please read the LocalView manual or contact the Socomec customer service.
Dry Contact Setting
Setup items
Selectable value
Default value
Dry
Contact
1 - Input
Option 1*: Disable/ ROO/ RPO/ Remote
shutdown/ Forced bypass/ On generator
Option 2: 0-999s (per step: 1 sec)
Option 3: Normal open/Normal close
Disable
Dry
Contact
2 - Output
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS
OK/ Load protected/ Load powered/ General alarm/
Overload alarm / Backfeed
On batt.
Dry
Contact
3 - Output
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS
OK/ Load protected/ Load powered/ General alarm/
Overload alarm / Backfeed
Low batt.
Dry
Contact
4 - Output
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS
OK/ Load protected/ Load powered/ General alarm/
Overload alarm / Backfeed
General alarm
Remote
Control
Option 1: REPO/ ROO
Option 2: Normally open/ Normally closed (For REPO)
or delay time 0-999sec (step: 1 sec)
Option 3: Normally open/ Normally closed (For ROO)
REPO/
NO
*: For detailed information about option 1, please contact service personnel.
Component Life Prediction
Setup Item
Selectable Value
Default Value
Fan Life Prediction
No/ Yes
No