NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
31
EN
Alarm
When any external battery pack connected to the UPS has the following problems,
the UPS system will sound an alarm. Please see the table below.
No.
External Battery
Pack Status
Description
1
Battery Mode
The alarm beeps once every 2 seconds.
2
Battery Low Warning
The alarm beeps once every 0.5 seconds.
3
Battery Missing/
Weak Battery/ Battery
Replacement
The alarm beeps once every 2 seconds.
4
Overload
• Overload_105%~125%: The alarm
beeps once every 2 seconds.
• Overload_125%~150%: The alarm
beeps once every 0.5 seconds.
5
Fault
The alarm beeps continuously for 5
seconds when the UPS detects an internal
fault. After the 5-second long beep, the
alarm beeps once every 2 seconds.
After reconnecting or replacing the batteries, it might take a while for the
UPS to switch off the alarm automatically. If, after a period of time, the
audible alarm continues, please manually initiate a battery test. Please
follow the route below to execute the manual battery test in order to clear
the alarm.
Route: press the button
for 0.1 seconds
→
tap the icon
Maintenance
→
select
Test
→
select Start Battery Test. For relevant information, please refer to 9.2 Main
Menu.