NETYS RT Hot Swap 7 - 11 kVA - 551574B - SOCOMEC
57
EN
You can choose the setup items such as Output, Input, ECO Mode, Parallel, On/ Off
Settings, Battery, General, Dry Contact Setting and Component Life Prediction to
set up relevant settings. For more information about the Setting Menu, please refer
to the tables below for each setup item’s relevant default value and selectable value.
Output
Setup Items
Selectable Value
Default
Output Phase
1-phase
1-phase
Output Voltage
200V, 208V, 220V,
230V, 240V
230V
Output Frequency
Auto*
1
/ Converter-50Hz*
2
/
Converter-60Hz*
2
Auto
Output Sync.
Freq. Range
±0.5/ 1/ 3/ 5Hz
±3Hz
Output Freq.
Slew Rate
0.5 / 1 / 2 Hz/ sec.
1 Hz/sec.
Output Mode
Industrial/ IT
IT
Standby Mode
No output/ Bypass output
No output
Overload Alarm
30-105% (per step: 5%)
105%
*1: When the Output Frequency is set as Auto, the output frequency will vary
according to the bypass frequency. If the bypass frequency is ≥ 55Hz, the Free_
Run_Frequency/ Cold_Start_Frequency will be set as 60Hz.
If the bypass frequency is < 55Hz, the Free_Run_Frequency/ Cold_Start_
Frequency will be set as 50Hz.
When the Output Frequency is set as Auto and the Bypass Output under
the Standby Mode item is set as Enable, the bypass output range will be
the same as the Output Sync. Freq. Range.
*2: When the Output Frequency is set as Converter-50Hz/ Converter-60Hz,
the UPS will enter the Frequency Conversion mode and the bypass output
will become Disable.