5.9.2.
Standard configuration
SW1
SW2
Relay contact
OFF
OFF
NO
ON
OFF
NC
GND
-R: Relay ground contact
Common
: 12~24 V DC
R1
General alarm
R2
No mains
R3
Battery low
R4
On by-pass
R5
Overload
R6
Overtemperature
Input
: Remote shutdown or battery test
5.9.3.
Customized configuration for relay and/or input contacts
Connect Tx to pin 2, Rx to pin 3 and GND-C to pin 5 of the computer’s RS232 port.
In Windows, start the Hyper-Terminal application and proceed to open the
specified COM port.
Set the following properties: Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit:
1, Flow Control: None.
Configuration.
Press <Enter> to display the main menu of the relay card.
UPS Relay Card
Firmware Version: Relay Card V1.4
[1] . Customize Output Relay
[2] . Configure Input Signal
[3] . Customize Normal Open or Normal Close
[0] . Quit
Please Enter Your Choice
>