3.3 ENVIRONMENTAL REQUISITES.
• The recommended operating temperature, humidity and altitude values are listed in the technical specifica-
tions table (see chapter 11). Cooling systems may be required to maintain these values.
• Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust
or chemical solutions).
• The UPS is not designed for outdoor use.
• Do not expose the UPS to direct sunlight or to sources of excessive heat.
• A space of at least 25 cm must be left at the back for adequate ventilation (see figure .-1).
• The UPS switches are accessed from the front; however, a space of at least 1.5 metres should be left at the
front of the UPS for maintenance purposes. It is also recommended to ensure that the cable connections are
sufficiently long and flexible so that the unit can be extracted during maintenance (see figure .-2).
• If it is not possible to leave sufficient space at the front, adequate access must be ensured from both sides.