MASTERYS BC
from 15 to 20 kVA
27
ENGLISH
6
MIMIC PANEL
6.1.3.1 “Alarms” menu
This menu displays all the alarms that are active at the time of access. The alarms menu is activated automati-
cally when an alarm condition occurs.
ALARMS menu
Code
Mimic panel message
Description
A00
GENERAL ALARM
At least one alarm is present
A01
BATTERY ALARM
Battery circuit failure or faulty operation.
A02
OUT OVERLOAD
Power required in output over the limits.
A06
VAUX OUT OF TOL
The voltage or frequency limits accepted by the bypass have been exceeded.
A07
OVER TEMPERATURE
Temperature excessive or ventilation problems.
A08
MAINTEN. BY-PASS
Active bypass procedure
A17
IMPROPER USE
Improper conditions of use verified (load, mains, temperature).
A18
OVERLOAD OFF INV
Inverter shutdown due to overload.
A20
WRONG CONFIG
Error in the configuration parameters (e.g. different between several UPS units
in parallel).
A22
MAINS OUT OF TOL
The voltage or frequency limits accepted by the rectifier have been exceeded
A2
RECTIFIER ALARM
Rectifier fault
A25
INVERTER ALARM
Inverter fault
A26
BATT CHARGER ALM
Battery charger fault
A29
BY-PASS ALARM
Bypass fault
A0
OVERLOAD STOP
The duration of the overload has inhibited the bypass.
A8
EXTERNAL ALARM 1
Signalling from ADC input
A9
EXTERNAL ALARM 2
Signalling from ADC input
A40
EXTERNAL ALARM
Signalling from ADC input
A41
EXTERNAL ALARM 4
Signalling from ADC input
A42
E-SERVICE ALARM
Alarm that generates automatic sending of a signal to the support centre
(if the service has been activated)
A4
REDUNDANCY LOST
The power required by the load no longer allows the preset redundancy N+x
(signalling for UPS units in parallel) to be maintained.
A44
SERVICE CHECK
Notification that the periodic service check is overdue
A49
BATT. DISCHARGED
The energy available in the battery has been used up.
A51
OPTIONAL BOARD ALM
Fault in the optional cards in the slots.
A58
ESD ACTIVATED
The remote emergency shutdown command has been activated.
A59
BATTERY CIRCUIT OPEN
The battery switch is open.
A60
FAN FAILURE
Fans faulty or blocked
A61
PHASE ROT FAILURE
Wrong phase cycle direction