MASTERYS BC
from 15 to 20 kVA
26
IT
ALIANOENGLISH
Meaning of the status light bar
Colour
Condition displayed
RED flashing
Imminent shutdown alarm (the load will be disconnected in a few minutes)
RED
Load not powered or battery circuit open
YELLOW flashing
Alarm indicating request for ordinary maintenance after over 25.000-0.000 hours of operation
according to conditions of use (type of load, temperature), (L7 flashing and alarm A44) UPS in
stand by
YELLOW
Load on battery or battery discharging if LED 2 is on steady
YELLOW
On automatic bypass if LED 5 is on steady
YELLOW
End of First maintenance period (10.000 hours) UPS in maintenance mode
GREEN flashing
Battery Test in progress
GREEN
Load powered by the inverter or in high efficiency mode
6.1.2 Meaning of the status light bar.
The light bar
B
(figure 6.1-1)provides an immediate indication of the condition of the power supply to the load:
• Red: power supply not present or shutdown imminent.
• Yellow: power supply present but unstable or temporary.
• Green: power supply sure and regular.
6
MIMIC PANEL
6.1.3 Display menu.
This paragraph describes the menus available on the mimic panel and their functions.
The displays are organised into menus and submenus as shown in the figure:
• to access a menu press the
ENTER
key
• to return to the higher level press
ESC
key
• Use the
UP
and
DOWN
keys to scroll the information available at a particular level.
MAIN
1 ALARMS
2 MEASUREMENTS
3 COMMANDS
4 PARAMETERS
5 SERVICE
3.1 IMMEDIATE COMMANDS
3.2 EXTENDED COMMANDS
4.1 UPS CURRENT DATA
5.1 UPS SETTING
5.2 CIM ALARMS CODE
5.3 WARRANTY CODE