4. 2.1. Installation on raised flooring
If Green Power 2.0 is to be installed on raised flooring, the SOCOMEC ad
-
justable frame (figure 4.2.1-1) must be used to support the weight of the unit
(figure 4.2.1-2).
refer to the relevant installation manual provided in the packaging for
information on frame assembly operations.
Allow for small openings in the floor panels to ensure the air flow at the front
(figure 4.2.1-3).
4. 2.2. Installation over a tunnel
4. R
equiSiteS
green power
2.0
cool
air
cool
air
door
4. 2.3. Heat loss and ventilation characteristics
kVa
air flow
Total air
flow
Heat losses at full load MaX.
at nominal / worst case
bottom
Mid height
kW
BTU/h
UPS 600
45 % *
55 % *
6750 m3/h
31800 / 39000
108505 / 133074
Bypass 600/800
100% *
0 % *
900 m3/h
3640
12459
Bypass 900/1200
2000 m3/h
5260
17973
Bypass 1500/2000
2200 m3/h
11600
36120
Bypass 2400
2200 m3/h
16700
50101
*
of Total air
flow