34
Green Po
wer 2.0 600 k
VA
- Ref.: INMGP2601410-GB_12
8. 1. s
torage
The duration of storage lead batteries must not exceed 6 months in appropriate storage conditions. The bat-
teries should be stored away from bad weather in space whose average temperature is between 30 °C and
-5 °C, with a maximum temperature below 40 °C. A battery is Rechargeable considered without significant
decrease in reliability, while his last refill does not date from more than 6 months.
8. 2. r
eplacement
of
batterIes
When replacing the batteries, please use the same type and number of battery blocks.
Do not dispose of into a fire due to risk of explosion. Do not try to open or break up batteries. The
electrolyte is toxic and may cause acid projections or injuries.
for this operation, we recommend that you contact a SocoMec servicing technician.
8. baTTery
8. 3. h
anDlIng
of
battery
cabInet
Handling from underneath
Handling can be from the bottom using a lifting truck. Front, rear as well as side bottom panels are available on
the top of the cabinet.
Handling from above
Handling can be by using 4 slings that are at least 1 meter long. The total weight shall not exceed 1500 kg, i.e.
375 kg per eye screw, so please adapt to the weight to be lifted accordingly.
8. 4. D
ImensIons
anD
weIghts
of
the
battery
cabInet
cabinet
800
1000
Maximum weight for transport (kg)
1700
1800
Maximum weight of blocks (kg)
1450
1500
Maximum weight per shelf (kg)
350
380
WIDTH (mm)
800
1 000
DEPTH (mm)
- floor requirement
815
- Overall dimensions with door handle
830
- door, handle and rear panel excluded
800
HEIGHT (mm)
1925
8. 5. b
attery
cabInets
fIxIng
for batteries on racks or in cabinets, the cabinet must be fixed to the floor to prevent it from falling
over. each cabinet is fitted with pre-drilled feet - See § 5.6.
feet of battery cabinet: same as Green Power 2.0 feet. (See §
"14. 6. Plan 6: Battery Floor fixing"
)
When the battery cabinet is installed, cut and remove the plastic fastening of battery cells in order to
release the safety valve