36
Green Po
wer 2.0 600 k
VA
- Ref.: INMGP2601410-GB_12
8. 8. b
attery
characterIstIcs
8. 8.1. Technical specifications
Dimensions (WxDxH):
800 x 830 x 1925 1000 x 830 x 1925
Weight (with packaging):
< 1550 kg
Protection level:
ip 20
Operating temperature:
0÷40 °c
(15÷25 °c recommended for longer battery life)
Storage and transport temperature
1
:
-5 °c ÷ +40 °c max
(recommended 25 °c)
Relative humidity (condensation-free):
up to 95%
Battery recharging:
Tambient ≤ 25 °C:
every 6 months
25 °C ≤ Tambient ≤ 30 °C:
every 4 months
30 °C ≤ Tambient ≤ 35 °C:
every 3 months
35 °C ≤ Tambient ≤ 40 °C:
every 2 months
Tambient > 40 °C:
not recommended
UPS output Power kW:
Battery block number:
540
<
p
≤
600
43
480
<
p
≤
540
from 39 to 43
p
≤
480
from 36 to 43
1
general indication for the application of lead batteries. for further details, see the battery manufacturer’s indications.
8. 8.2. Reliability
Conforms to Standards:
iec 50272-2, iec 62040-1-1
8.