28
Green Po
wer 2.0 600 k
VA
- Ref.: INMGP2601410-GB_12
X10
X10
X10
X10
X10
X40
Q4
Q5
Q20
KM40
Q2
X30
X30
X30
X30
X30
X45
Q3
X50
UNIT
2
BYPASS CENTRALISED CABINET
UNIT
3
UNIT
4
UNIT
N
7. 2.3. Unit connection in C3
7. 2.4. Centralised Bypass connection in C3
INPUT TO RECTIFIER AND BYPASS MAINS
TO LOAD
PkVa name
Designation
copper
termination
0
hole
screw
Max cross
section
coupling
torque
200
à
800
X45/L
Unit input
100 x 5 mm
3 x 13
M12
2x 3 x 240 mm²
70 Nm
X45/N
185 x 5 mm
5 x 13
M12
5 x 240 mm²
70 Nm
X40
Mains input
185 x 5 mm
4 x 13
M12
4 x 240 mm²
70 Nm
X50
Load output
185 x 5 mm
4 x 13
M12
4 x 240 mm²
70 Nm
PE
Protective conductor
50 x 5 mm
6 x 13
M12
6 x 150 mm²
70 Nm
900
à
1200
X45/L
Unit input
100 x 10 mm
3 x 13
M12
2x 3 x 240 mm²
70 Nm
X45/N
100 x 10 mm
10 x 13
M12
2x 10 x 240 mm²
70 Nm
X40
Mains input
100 x 10 mm
4 x 15
M14
2x 4 x 240 mm²
110 Nm
X50
Load output
100 x 10 mm*
4 x 15
M14
2x 4 x 240 mm²
110 Nm
PE
Protective conductor
50 x 5 mm*
6 x 13
M12
6 x 240 mm²
70 Nm
*Copper extension terminals (100x10, 7 holes *13) are to be moved from X40 to X50 if cable input is from the top.
7. Connection
MaIns
oUTPUT
7. 2.3-1
X5
X4
X1
X40
X20
-
X20 +
X30
L1
L2
L3
N
L1
L2
L3
N
N
N
L1
L3
L1
L2
L3
L1
L2
L2
L3
N = max 4 modules