Flashing LED
Stable LED
Steps involved in the auto-discovery process:
Press
3 sec.
≤ 120 sec
3
Press
3 sec.
4
a
Press
3 sec.
5
a
6
1. Start the auto-discovery of all devices connected to the Digiware or RS485 buses, by pressing the ADDR. button
for 3 seconds.
2. “COM” LEDs of all devices will start blinking synchronously during the process. If com LEDs are not blinking, there
could be a configuration issue (inconsistent baudrate between M-xx gateway and slave device etc.).
3. After approximately 1 minute, some address conflicts have been detected, and the COM LED of the M-xx gateway
as well as slave devices is lit and stable.
4a/5a. Press the front button on each slave device that has a fixed COM LED, for at least 2 seconds.
4b/5b. COM LEDs of the modules start blinking again.
6. COM LED of the M-xx gateway starts blinking again, and slave devices can now communicate with the M-xx
gateway.