13. 10-STEP COMMISSIONING CHECKLIST FOR YOUR
DIGIWARE SYSTEM
1) Auto-discovery from M-50/M-70 push button or from EasyConfig System software.
2) Configuration of DIRIS Digiware U and I modules via EasyConfig System software.
3) Connection to the webserver (default IP address is 192.168.0.4).
4) Change default passwords for Admin, Advanced and Cyber security profiles.
5) Connect to the Cyber security profile and generate the passphrase in case you lose your password.
6) Device discovery via “Devices” tab
“Sources”.
7) Change load names and usages if necessary.
8) Optional: Hierarchy configuration (M-70 only).
9) Optional: Photoview configuration (M-70 only).
10) Configuration of IP configuration and communication protocols via “Protocols” menu.
Frequently Asked Questions
What happens if you lose your password ?
- If the Admin or Advanced Users lose their password, they can be changed from the Cyber security profile.
- If the Cyber security user loses his password, the passphrase can be used to create a new password.
- If the passphrase was lost, the only option is to reset the M-50/M-70 gateway to factory default settings.
How can I configure my IP configuration and communication protocols for my system ?
- Using EasyConfig System.
- Or directly from the web server under the “Protocols” menu. Do not forget to reboot the M-50/M-70 gateway
after modifying the IP configuration.
Why is the ALARM LED on the M-50/M-70 flashing ?
- If this is the first time you are using the DIRIS Digiware M-50/M-70 gateway, it could be that the default
passwords for the Advanced User, Admin and Cyber security profiles have not been changed yet. The
“Password Alert” system alarm will be active until passwords are changed.
The Auto-discovery process is finished, yet some slave devices have not been detected.
If slave devices have not been detected, it could be because the Auto-discovery mode is set to “FAST”, which
only detects DIRIS Digiware modules, DIRIS B and DIRIS A-40 measuring devices. Use EasyConfig System to
change the Auto-discovery mode to “FULL” to discovery all devices.