ATyS t M - 542931D - SOCOMEC
8
EN
3. QUICK START
3.1. Quick Start ATy
S t M
quick start
40 - 160A (4P)
EN
ATyS
t
M
Automatic
Transfer Switching Equipment
Preliminary operations
Check the following upon delivery and after removal of the
packaging:
n
Packaging and contents are in good condition.
n
The product reference corresponds to the order.
n
Contents should include:
Qty 1 x ATyS M
Qty 1 x Emergency handle extension rod
Qty 1 x Set of terminals
Quick Start instruction sheet
Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
n
This product must always be installed and commissioned
by qualified and approved personnel.
n
Maintenance and servicing operations should be
performed by trained and authorised personnel.
n
Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
n
Always use an appropriate voltage detection device to
confirm the absence of voltage.
n
Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Risk of damaging the device
n
In case the product is dropped or damaged in any way it
is recommended to replace the complete product.
Accessories
n
Bridging bars 125A or 160A.
n
Control voltage transformer (400Vac -> 230Vac).
n
Voltage sensing and power supply tap.
n
Terminal shrouds.
n
Auxilliary contact blocks.
n
Polycarbonate enclosure.
n
Polycarbonate extension box.
n
Power Connection Terminals.
n
Sealable cover.
Printing informations:
1 color Black. White paper 90g/m
2
.
Printing size: 420x297. Final size 210x297. This page visible first.
A separate sheet for each language.
Non contractual document.
Subject to change without notice.
STEP 1
Cabinet / Back
Plate Installation
STEP 3
CONTROL /
AUX POWER
terminal
connections
STEP 2
Connecting the
POWER section
STEP 4
CHECK
STEP 5
Programming
Installation and Commissioning
STEP 6A
Automatic Operation
STEP 6C
Padlocking
STEP 6B
Emergency Manual
Operation
STEP 3
STEP 6A
Check
Automatic
operation
STEP 5
Programming
CONTROL / AUX POWER Terminals and wiring
■
Auto conf. of the network voltage and frequency.
1. Put dipswitch A-B to
position B. (All Led's
should be blinking).
2. When the LED’s
become a steady light
ON, confi guration of
the network is ready.
3. Put dipswitch A-B
back to A.
■
Set dip switches C-D, E-F, G-H
■
Set potentiometer for priority
supply "Failure and Return Timer"
FT: 0-30 sec / RT: 0-30 min.
Close the front cover as
shown to put the product
into automatic mode.
Ensure that the product is in Manual Mode
(front cover open).
• C: ΔU 10%/ΔF 5%
• D: ΔU 20%/ΔF 10%
HYST: 20 % of
D
U/F settings
•
E: No stop in O position
•
F: 2s stop in 0 position
•
G: With priority
•
H: Without priority
STEP 4
Whilst in manual mode, check
the wiring and if ok power up
the product.
•
A: Ready
•
B: Auto Conf
(Auto-configuration)
Setting mode A-B
Thresholds C-D
■
Source availability LED's
Stop in 0 position E-F
Priority G-H
Type Terminal
no.
Description
Characte-
ristics
Recommanded
connection
cross-section
Inputs
207
Common
Dry
potential
free contact
0,5 to 2,5 mm²
(rigid)
0,5 to 1,5mm²
(stranded)
208
Position 0 order
209
Open SI priority.
Closed S2
priority.
210
Inhibition ATS
Outputs
63/64
Open: SI and S2
NOT available.
Closed: SI or S2
available
Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W
or 125VA
Umax : 30Vdc
or 230Vac
73/74
Not used
Auxiliary
contacts
unit.
11/12/14 Position I
Dry potential
free contact
250Vac 5A
AC1
24Vdc 2A
21/22/24 Position II
01/02/04 Position 0
Source
LED ON Source 1
available
Source 2
available
LED OFF Source 1 not
availlable
Source 2 not
availlable
LED
blinking
- a timer is
counting
down
- a timer is
counting
down
Slotted head 3mm 0,5 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
STEP 6B
Manual operation
•
Open the front cover as
shown to put into manual
mode.
•
Use the handle situated in
the front panel under the cover to operate the
transfer switch.
•
Check the changeover switch position on the
indicator before operating.
To simplify operation
use the handle with the
extension provided.
(Max 8 Nm)
II
I
o
0,5 to 2,5 mm
2
#28 to #14 AWG
0,5 to 2,5 mm
2
#28 to #14 AWG
6 mm / 0,236"
Slotted head 2,5 mm
90º
90º
Extension
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
207208209210 63 64 73 74
6 mm /
Capacité de raccordement
0,236 "
# 20 to # 14 AWG
0,5 to 2,5 mm
0,5 to 1,5 mm
2
2
# 20 to # 16 AWG
Slotted head 3 mm
3,97 lb-in 0,5 Nm
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
2
4
6
8
1
3
5
7
I1 I2 I3
O1
207208209210 63 64 73 74
/
I1 I2 I3
O1 O2
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
not used
LOAD
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 1001
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
5 A AC1
250 Vac
22 24 21
11 14 12
01 04 02
1309 1011
www.socomec.com
www.socomec.com/operating-instructions
To download, brochures, catalogues and technical manuals.
Pozidriv PZ2 - 1 Nm
Use 20mm
screws for
1 module
Use 35mm
screws for
2 modules
!
Auxiliary contacts:
Fitting of auxiliary contacts:
1309 1001 or 1309 1011
To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one
NO/NC changeover contact for each position (I-0-II). To install use the long screws supplied with
the module.
STEP 1
The ATyS M is delivered with
padlocking configured to the
O position.
To allow padlocking in all
positions (I - O - II), configure
the ATyS M as follows before
installation. (Screw is located
at the back of the product).
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in
0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in
0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in
0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in
0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in
0,25 Nm
2 X
Posidriv PZ2
OK
OK !
!
STEP 1
STEP 2
STEP 3
STEP 4
Posidriv PZ2
Posidriv PZ2
2,2 lb-in
0,25 Nm
2 X
Installation
Padlocking configuration
Caution: Ensure that the product is installed on a flat rigid surface.
MAX : 2
340
26
116
53
46
73,5
245
143
350
18
45
13
324
340
326
131,5
131,5
52
104
176
47
Recommended orientation
Recommended
Ok
Ok
Ok
Ok
Ok
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
2 clips de verrouillage
Posidriv PZ1
1 Nm
Tighten to avoid
movement on the DIN rail.
DIN RAIL
IEC 60715
6 mounting brackets
6x M6 screw - 2,5 Nm
2x
2x
STEP 2
Power Terminal Connections
Source supply side
Hexagonal Metric
Allen size 4
5,0 Nm
It is essential to tighten all used
terminals, with cables and/or
bridging bars, before use.
Allen size 4
Hexagonal Metric
44,1 lb-in
5,0 Nm
15 mm /
0,59 "
# 8 to # 00 AWG
10 to 70 mm
2
6 to 70 mm
2
*
# 10 to # 00 AWG
!
X8
Allen size 4
Hexagonal Metric
44,1 lb-in
5,0 Nm
15 mm /
0,59 "
# 8 to # 00 AWG
10 to 70 mm
2
6 to 70 mm
2
*
# 10 to # 00 AWG
!
X8
Voltage taps provide 2x ≤ 1.5mm
2
connections.
They can be fitted in any terminals on the source
supply side. Do not use on the load side when
equipped with a bridging bar.
Load side
bridging bar.
125A: 1309 4006
160A: 1309 4016
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²
6 mm
10 to
70 mm²
15mm
MAX : 2
340
26
116
53
46
73,5
245
143
350
18
45
13
324
!
STEP 6C
Padlocking mode
1x 4-8 mm
•
In order to padlock put the
product in manual mode.
•
Pull the locking mecha-
nism and insert a padlock
as shown.
•
As standard padlocking in the 0 position.
Configurable to I-0-II (see step 1).
Step 1
Step 2
Step 3