ATyS t M - 542931D - SOCOMEC
26
EN
13.4. Programming
Whilst in manual mode check the wiring and installation . If ok power up the product .
This product must always be put into service by qualified and approved personal.
The LED signalling is only active when the product supply is on (supply LED lit) .
To set the dip switches, it is necessary to open the AUTO/MANU cover .
The commissioning must always result in having at least 1 LED source available lit..
Therefore, the voltage and frequency must be within the defined thresholds.
Any action on the potentiometers changes the settings, even if the cover is closed.
13.4.1.
Auto-configuration
Once the product is connected, you can configure automatically its nominal voltage & nominal frequency.
Therefore, while front cover is open:
1 . Put dip switch A-B in position B .
2 . All leds are blinking .
3 . All leds are on, not blinking anymore .
4 .
Put dip switch A-B in position A: product is ready to work.
The LED signalling and operation is only active when the product supply is available .
To set the dip switches, it is necessary to open the Auto/Manual cover .
13.4.2.
Sealable configuration cover
Configuration settings may be protected by means of a sealable cover.
Refer to section «5. Optional accessories», page 11.