9. INSTALLATION OF OPTIONAL ACCESSORIES
9.1.
Auxilliary contacts
Ref. 1309 1001 or ref. 1309 1011.
To fit an additional AC, the switch must first be put in the 0 position. An auxiliary contact module comprises: one NO/NC
or NOC changeover contact for each position (I-0-II) . To install use the screws supplied with the module .
One module is factory fitted.
10 mm
0,5 to 2 .5 mm²
solid
stranded
0,5 to 1 .5 mm²
PUSH-IN
Use 20mm
screws for
1 module
Use 35mm
screws for
2 modules
Posidriv PZ2
1 Nm
9.2.
Voltage sensing and power supply tap
Ref . 1399 4006 .
This provides 2 connection terminals for conductors with cross-section ≤ 1.5 mm².
The single pole terminals can be fitted in any of the terminal cages without reducing the cage connection capacity.
2 parts/ref . Do not use in case of use of the bridging bar .
6 mm
Slotted head 3,5 mm
0,45 Nm
0,5 to 2,5 mm²
0,5 to 1,5 mm²