background image

ATyS t M - 542931D - SOCOMEC

9

EN

quick start

40 - 160A (4P)

EN

ATyS 

t

 M

Automatic  

Transfer Switching Equipment

 Preliminary operations 

Check the following upon delivery and after removal of the 

packaging:

n

 

 Packaging and contents are in good condition.

n

 

 The product reference corresponds to the order.

n

 

 Contents should include:

Qty 1 x ATyS M
Qty 1 x Emergency handle extension rod
Qty 1 x Set of terminals
Quick Start instruction sheet

 Warning 

 

Risk of electrocution, burns or injury to persons and / 

or damage to equipment.
This Quick Start is intended for personnel trained in the 

installation and commissioning of this product. For further 

details refer to the product instruction manual available on 

the SOCOMEC website.

n

  This product must always be installed and commissioned 

by qualified and approved personnel.

n

  Maintenance and servicing operations should be 

performed by trained and authorised personnel.

n

  Do not handle any control or power cables connected to 

the product when voltage may be, or may become present 

on the product, directly through the mains or indirectly 

through external circuits.

n

 

 Always use an appropriate voltage detection device to 

confirm the absence of voltage.

n

 

 Ensure that no metal objects are allowed to fall in the 

cabinet (risk of electrical arcing).

Failure to observe good enginering practises as well as to 

follow these safety instructions may expose the user and 

others to serious injury or death.

 

Risk of damaging the device

n

 

 In case the product is dropped or damaged in any way it 

is recommended to replace the complete product.

 Accessories 

n

 

 Bridging bars 125A or 160A.

n

 

 Control voltage transformer (400Vac -> 230Vac).

n

 

 Voltage sensing and power supply tap.

n

 

 Terminal shrouds.

n

 

Auxilliary contact blocks.

n

 

 Polycarbonate enclosure.

n

 

 Polycarbonate extension box.

n

 

 Power Connection Terminals.

n

 

Sealable cover.

Printing informations:

 1 color Black. White paper 90g/m

2

Printing size: 420x297. Final size 210x297. This page visible first.

A separate sheet for each language.

Non contractual document.

Subject to change without notice.

STEP 1

 

Cabinet / Back 

Plate Installation

STEP 3

 

CONTROL /  

AUX POWER 

terminal 

connections

STEP 2

 

Connecting the 

POWER section

STEP 4

 

CHECK

STEP 5

 

Programming

Installation and Commissioning

STEP 6A

 

Automatic Operation

STEP 6C

 

Padlocking

STEP 6B

 

Emergency Manual 

Operation

STEP 3

STEP 6A

Check

Automatic 

operation

STEP 5

Programming

CONTROL / AUX POWER Terminals and wiring

 

Auto conf. of the network voltage and frequency.

1. Put dipswitch A-B to 

position B. (All Led's 

should be blinking).

2.  When the LED’s 

become a steady light 

ON, confi guration of 

the network is ready.

3.  Put dipswitch A-B 

back to A.

 

Set dip switches C-D, E-F, G-H

 

Set potentiometer for priority 

supply "Failure and Return Timer"
FT: 0-30 sec / RT: 0-30 min.

Close the front cover as 

shown to put the product 

into automatic mode.

Ensure that the product is in Manual Mode 

(front cover open).

• C: ΔU 10%/ΔF 5%

• D: ΔU 20%/ΔF 10%

HYST: 20 % of 

D

U/F settings

• 

E: No stop in O position

• 

F: 2s stop in 0 position

• 

G: With priority

• 

H: Without priority

STEP 4

Whilst in manual mode, check 

the wiring and if ok power up 

the product.  

• 

A: Ready

• 

B: Auto Conf  

(Auto-configuration)

Setting mode A-B

Thresholds C-D

 

Source availability LED's

Stop in 0 position E-F

Priority G-H

Type Terminal 

no.

Description

Characte-

ristics

Recommanded 

connection  

cross-section

Inputs

207

Common

Dry 
potential 
free contact

0,5 to 2,5 mm²  
(rigid)

0,5 to 1,5mm² 
(stranded)

208

Position 0 order

209

Open SI priority.
Closed S2 

priority.

210

Inhibition ATS

Outputs

63/64

Open: SI and S2 

NOT available.
Closed: SI or S2 

available

Resistive load
2A 30 Vdc
0.5A 230Vac
Pmax : 60W 
or 125VA
Umax : 30Vdc 
or 230Vac

73/74

Not used

Auxiliary 
contacts 
unit.

11/12/14 Position I

Dry potential 

free contact 

 

250Vac 5A 
AC1 
24Vdc 2A

21/22/24 Position II

01/02/04 Position 0

Source

LED ON Source 1 

available

Source 2 

available

LED OFF Source 1 not 

availlable

Source 2 not 

availlable

LED 

blinking

-  a timer is 

counting 

down

-  a timer is 

counting 

down

Slotted head 3mm 0,5 Nm

0,5  to  2,5 mm²

0,5  to  1,5 mm²

6 mm

STEP 6B

Manual operation

• 

Open the front cover as 

shown to put into manual 

mode.

• 

Use the handle situated in 

the front panel under the cover to operate the 

transfer switch.

• 

Check the changeover switch position on the 

indicator before operating.

To simplify operation 

use the handle with the 

extension provided.

(Max 8 Nm)

II

I

o

  0,5 to 2,5 mm

2

  #28 to #14 AWG
  0,5 to 2,5 mm

2

  #28 to #14 AWG
       6 mm / 0,236"

Slotted head 2,5 mm

90º

90º

Extension

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

207208209210 63 64 73 74

6 mm /

Capacité de raccordement

 0,236 "

# 20 to  # 14 AWG

0,5  to  2,5 mm

0,5  to  1,5 mm

2

2

# 20 to # 16 AWG

Slotted head  3 mm

3,97 lb-in  0,5 Nm

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

2

4

6

8

1

3

5

7

I1 I2 I3

O1

207208209210 63 64 73 74

/

I1 I2 I3

O1 O2

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

not used

LOAD

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

1309 1001

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

5 A AC1
250 Vac

22 24 21

11 14 12

01 04 02

1309 1011

www.socomec.com

www.socomec.com/operating-instructions

To download, brochures, catalogues and technical manuals.

Pozidriv PZ2 - 1 Nm

Use 20mm 

screws for 

1 module

Use 35mm 

screws for 

2 modules

!

Auxiliary contacts: 

Fitting of auxiliary contacts: 

1309 1001 or 1309 1011

To fit an AC, the switch must first be put in position 0. An auxiliary contact module comprises: one 

NO/NC changeover contact for each position (I-0-II). To install use the long screws supplied with 

the module. 

STEP 1

  

The ATyS M is delivered with 

padlocking configured to the 

O position.

  

To allow padlocking in all 

positions (I - O - II), configure 

the ATyS M as follows before 

installation. (Screw is located 

at the back of the product).

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Posidriv  PZ2 

OK

OK !

!

STEP 1

STEP 2

STEP 3

STEP 4

Posidriv  PZ2 

Posidriv  PZ2 

2,2 lb-in

  0,25 Nm

2 X

Installation

Padlocking configuration

Caution: Ensure that the product is installed on a flat rigid surface.

MAX : 2

340

26

116

53

46

73,5

245

143

350

18

45

13

324

340

326

131,5

131,5

52

104

176

47

Recommended orientation

Recommended

Ok

Ok

Ok

Ok

Ok

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

OK

2 clips de verrouillage

Posidriv  PZ1

1 Nm

 Tighten to avoid 

movement on the DIN rail.

DIN RAIL
IEC 60715

6 mounting brackets

6x M6 screw - 2,5 Nm

2x

2x

STEP 2

Power Terminal Connections

Source supply side

Hexagonal Metric

Allen size 4

5,0 Nm

  It is essential to tighten all used 

terminals, with cables and/or 

bridging bars, before use.

Allen size 4

Hexagonal Metric

44,1 lb-in

  5,0 Nm

15 mm /

 0,59 "

# 8  to  # 00 AWG

10  to  70 mm

2

6  to  70 mm

2

*

# 10 to # 00 AWG

!

X8

Allen size 4

Hexagonal Metric

44,1 lb-in

  5,0 Nm

15 mm /

 0,59 "

# 8  to  # 00 AWG

10  to  70 mm

2

6  to  70 mm

2

*

# 10 to # 00 AWG

!

X8

Voltage taps provide 2x ≤ 1.5mm

2

 connections. 

They can be fitted in any terminals on the source 

supply side. Do not use on the load side when 

equipped with a bridging bar.

Load side 

bridging bar.
125A: 1309 4006
160A: 1309 4016

Slotted head  3,5 mm

0,45 Nm

0,5  to  2,5 mm²

0,5  to  1,5 mm²

6 mm

10 to 
70 mm²

15mm

MAX : 2

340

26

116

53

46

73,5

245

143

350

18

45

13

324

!

STEP 6C

Padlocking mode

1x 4-8 mm

• 

In order to padlock put the 

product in manual mode.

• 

Pull the locking mecha-

nism and insert a padlock 

as shown.

• 

As standard padlocking in the 0 position. 

Configurable to I-0-II (see step 1).

Step 1

Step 2

Step 3

CORPORATE HQ CONTACT:  

SOCOMEC SAS, 1-4 RUE DE WESTHOUSE, 67235 BENFELD, FRANCE

542930E

Summary of Contents for ATyS p

Page 1: ...Automatic Transfer Switching Equipment ATyS t M INSTALLATION AND OPERATING MANUAL EN ...

Page 2: ... mounted 15 9 INSTALLATION OF OPTIONAL ACCESSORIES 16 9 1 Auxilliary contacts 16 9 2 Voltage sensing and power supply tap 16 9 3 Bridging bars 4P 17 9 4 Terminal shrouds 17 9 5 Sealable cover 17 10 INSTALLING WITHIN THE ATYS M ENCLOSURE 18 10 1 Polycarbonate enclosure 18 10 1 1 Wiring in a polycarbonate enclosure 18 10 1 2 Extension unit 18 11 CONNECTION OF THE POWER CIRCUITS 19 11 1 Ratings cross...

Page 3: ... 24 13 1 2 Reset 24 13 2 Manual mode 25 13 2 1 Manual switching 25 13 3 Padlocking 25 13 4 Programming 26 13 4 1 Auto configuration 26 13 4 2 Sealable configuration cover 26 13 5 Automatic mode 27 13 5 1 Sealable Auto Manual cover 27 13 6 Possible actions 27 14 PREVENTATIVE MAINTENANCE 28 15 TROUBLESHOOTING GUIDE 29 ...

Page 4: ...mage to equipment This instruction manual must be made accessible so as to be easily available to anyone who may need to read it in relation with the ATyS The ATyS meets the European Directives governing this type of product and includes CE marking on each product No covers other than that for auto manu on the ATyS should be opened with or without voltage as there may still be dangerous voltages i...

Page 5: ...sible position indication I 0 II An inherent failsafe mechanical interlock Stable positions I 0 II non affected by typical vibration and shocks Constant pressure on the contacts non affected by network voltage Energy Efficient with virtually no consumption whilst on the normal alternate or off positions Extremely rugged error free and built in padlocking facility configurable Straight forward inst...

Page 6: ...TRANSITION MOTORISED CHANGEOVER SWITCH DUAL POWER SUPPLY BUILT IN ATS CONTROLLER COMMUNICATION Specific version Return to zero without external energy source TRIPPING A product for virtually all power changeover applications from 40 to 160 A Network Genset Genset Genset Network Network Applications with an External ATS Control Network Genset Network Network ATyS d M GS U P S Network Network Buildi...

Page 7: ...o switch By screen keyboard Vn Fn V threshold F threshold Driving with or without priority Adjustable operating timers Preset configuration Control type impulse or switch contactor DISPLAY Position fully visualised breaking LED source status automatic mode fault LED LED switch positions supply tests control V F timers number of operations last event REMOTE CONTROL Outputs Generator start stop orde...

Page 8: ...bject to change without notice STEP 1 Cabinet Back Plate Installation STEP 3 CONTROL AUX POWER terminal connections STEP 2 Connecting the POWER section STEP 4 CHECK STEP 5 Programming Installation and Commissioning STEP 6A Automatic Operation STEP 6C Padlocking STEP 6B Emergency Manual Operation STEP 3 STEP 6A Check Automatic operation STEP 5 Programming CONTROL AUX Auto conf of the network voltag...

Page 9: ...ll use the long screws supplied with the module STEP 1 The ATyS M is delivered with padlocking configured to the O position To allow padlocking in all positions I O II configure the ATyS M as follows before installation Screw is located at the back of the product Posidriv PZ2 OK OK STEP 1 STEP 2 STEP 3 STEP 4 Posidriv PZ2 Posidriv PZ2 2 2 lb in 0 25 Nm 2 X Posidriv PZ2 OK OK STEP 1 STEP 2 STEP 3 S...

Page 10: ...s 3 1 2 4 5 CAUTION Ensure that the load is connected to the top of the switch with the motorisation on the right hand side as shown 4 2 Specifications and advantages 1 Power section A fully integrated and interlocked transfer switch with high electrical performance offering microprocessor control and monitoring 2 Operation A flexible operating mechanism enabling quick motorised transfer in automa...

Page 11: ...94 4016 2 parts ref Double power supply DPS Allows an ATyS d M to be supplied by two 230 Vac 50 60 Hz networks Réf 1599 4001 Enclosure Fully dedicated to ATyS M use this polycarbonate enclosure provides easy access to a compact enclosed transfer switch HxWxD 385x385x193mm Ref 1309 9006 Extension unit Combined with the polycarbonate enclosure the extension box creates extra space for routing cables...

Page 12: ... protected short circuit withstand kA eff 50 50 50 50 50 40 Associated fuses gG DIN 40 63 80 100 125 160 Short circuit capacity Rated short term withstand current Icw 1s kA eff 4 4 4 4 4 4 Rated short term withstand current Icw 30ms kA eff 10 10 10 10 10 10 Switching time at In excluding loss of supply sensing time and excluding any delay timers applicable I II or II I ms 180 180 180 180 180 180 D...

Page 13: ...0 C with de rating see Technical Characteristics Altitude Up to 2000m Correction factors 2 000 m A 3 000 m 3 000 m A 4 000 m UE 0 95 0 80 Ie 0 85 0 85 Storage 1 year maximum Maximum storage temperature 55 C 80 humidity without condensation at 55 C ø 1 mm IP rating IP41 in the SOCOMEC polycarbonate modular enclosure see page page 18 IP2x for non enclosed modular product Protection class Class 1 ...

Page 14: ...P1 loosen the screw at the back of the product as shown below STEP2 slide the screw upwards STEP3 tighten the screw in the top position as shown 2 2x 3 Posidriv PZ2 2 2 lb in 0 25 Nm Posidriv PZ2 2x 1 Posidriv PZ2 2x 8 2 Recommanded orientation OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK Recommended Ok Ok Ok Ok Ok 8 3 Dimensions 8 4 B...

Page 15: ...ATyS t M 542931D SOCOMEC 15 EN 8 5 DIN rail mounted rrouillage Posidriv PZ1 1 Nm Tighten to avoid movement on the DIN rail DIN RAIL IEC 60715 ...

Page 16: ...he module One module is factory fitted 10mm 0 5 to 2 5 mm solid stranded 0 5 to 1 5 mm PUSH IN Use 20mm screws for 1 module Use 35mm screws for 2 modules Posidriv PZ2 1 Nm 9 2 Voltage sensing and power supply tap Ref 1399 4006 This provides 2 connection terminals for conductors with cross section 1 5mm The single pole terminals can be fitted in any of the terminal cages without reducing the cage c...

Page 17: ...5 7 LOAD LOAD Source I Source I Source II Source II Allen size 4 Hexagonal Metric 44 1 lb in 5 0 Nm 15 mm 0 59 8 to 00 AWG 10 to 70 mm2 6 to 70 mm2 10 to 00 AWG X Allen size 4 Hexagonal Metric 44 1 lb in 5 0 Nm 15 mm 0 59 8 to 00 AWG 10 to 70 mm2 6 to 70 mm2 10 to 00 AWG X8 Bridging bar 125A 1309 4006 160A 1309 4016 OK NOK Make sure that the bridging bar is fitted to the correct set of terminals T...

Page 18: ...ed size M6 50 mm minimum Weight between 8 and 10 kg depending on the accessories Only 1 aux contact block may be installed when using this enclosure 193 mm 225 mm M6 275 mm M6 385 mm 385 mm 10 1 1 Wiring in a polycarbonate enclosure Example Neutral on the right N N N Max cable size 25 mm 10 1 2 Extension unit Ref 1309 9007 Enables you to allocate additional space to the polycarobonate enclosure re...

Page 19: ...6 25 35 50 50 Max cable size recommended mm2 50 50 50 50 70 70 With extension unit Maximum cable size for rigid cable is 50 mm2 For larger terminations use the power connection terminals ref 1399 4017 Not compatible with aluminium cables 11 2 Parallel pole set up for a 4P device used in single phase Rating conversion table for use in single phase and two by two parallel pole set up Max ambient tem...

Page 20: ...the left or neutral on the right in advance and then wired accordingly The example below shows the wiring for a product configured with neutral on the left A new product must have the neutral configuration pre programmed as on the left or on the right at the first start up using a real not a recreated 3 phase neutral supply 11 3 1 1 Auto transformer connections Reference 1599 4121 I II 207 L32 L22...

Page 21: ...8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 I1 I2 I3 O1 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 5 A AC1 250 Vac 22 24 21 11 14 12 01 04 02 Ensure that the product is in Manual Mode front cover open Slotted head 3 mm 0 5 Nm 0 5 to 2 5 mm 0 5 to 1 5 mm 6 mm All pressure o...

Page 22: ... source 2 available position 2 source 1 available To restart the automatism you need to open the contact and to have an action to erase the fault manual mode inhibition mode priority change TYPE TERMINAL NO STATUS OF THE CONTACT DESCRIPTION OUTPUT CHARACTERISTICS RECOMMENDED CONNECTION CROSS SECTION Auxiliary contact block 1309 1001 11 12 14 11 14 12 Changeover switch in position I 250V AC 5A AC1 ...

Page 23: ...ct operating schedule Position I Position 0 Position II C A Position I C A Position 0 C A Position II 11 14 Closed 11 12 Open 01 04 Closed 01 02 Open 21 24 Closed 21 22 Open Position I Position 0 Position II C A Position I C A Position 0 C A Position II ...

Page 24: ...lock using a 1 x 8 mm max padlock 2 AUT MAN cover Open the cover to switch to manual mode Close the cover to return to automatic remote control mode Open and close the cover to clear faults 3 Auto Manual mode sensor 4 Switch position indicators Display of position I 0 II 5 Manual switching Insert the Allen key 5 0 mm provided and turn to switch manually Manual operation is not possible when padloc...

Page 25: ...tension that is delivered with the product Check the changeover switch position on the indicator situated on the front panel before making any operation From position I turn anti clockwise to get to position 0 From position 0 turn anti clockwise to get to position II From position II turn clockwise to get to position 0 From position 0 turn clockwise to get to position I Max 8 Nm Extension Do not f...

Page 26: ...lds Any action on the potentiometers changes the settings even if the cover is closed 13 4 1 Auto configuration Once the product is connected you can configure automatically its nominal voltage nominal frequency Therefore while front cover is open 1 Put dip switch A B in position B 2 All leds are blinking 3 All leds are on not blinking anymore 4 Put dip switch A B in position A product is ready to...

Page 27: ...de AUT LED lit 13 5 1 Sealable Auto Manual cover Auto Manu mode can be protected by sealing the standard Auto Manu cover as shown 13 6 Possible actions Once in automatic mode it is possible to Run a source I source loss sequence II start a restoration sequence source I source II Source I return source II Loss of source I source II AUTOMATIC MODE ...

Page 28: ...f the critical level and application where the product is installed should form an essential and integral part of the maintenance plan Good engineering practice is imperative whilst all necessary precautions must be taken to ensure that the intervention whether directly or indirectly remains safe in all aspects The use of any Megohmmeter is prohibited on this product as the connection terminals ar...

Page 29: ...s power terminals 1 and 7 on switch II The AUT LED is ON with manual operation cover closed The switch does not transfer after loss of priority source Check that the product is not in manual mode Automatic mode Cover closed Manual mode Cover open The AUT LED is ON Check that automatic operation has not been inhibited by an external order terminals 207 210 Check that the backup source is seen as av...

Page 30: ...542931D CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com ...

Reviews: