manualshive.com logo in svg
background image

User’s Guide

 

 

Industrial Conditioners 

 

GPI Series B Conditioners 

 

GPI Series 1 Conditioners 

 

2-15 kVA Single Phase Conditioners

  GPI Series 1 Conditioners 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

POWERVAR 

Single Phase 

Power Conditioners 

 

 
 
 
 
 
 
 
 

RoHS Compliant 

 
 
 
 
 

 
 

Содержание ABC10.0-2S

Страница 1: ...er s Guide Industrial Conditioners GPI Series B Conditioners GPI Series 1 Conditioners 2 15 kVA Single Phase Conditioners GPI Series 1 Conditioners POWERVAR Single Phase Power Conditioners RoHS Compliant ...

Страница 2: ...hanges may periodically be made to the information herein and such changes may be incorporated in new editions of the product and it s accompanying documentation without obligating POWERVAR to update information and or product that has been delivered earlier POWERVAR assumes no liability for typographical errors in this documentation POWERVAR shall not be liable for technical or editorial errors o...

Страница 3: ...ill not be exposed to excessive dust or moisture Make certain that there is adequate airflow around the unit If the unit has air vents do not place objects on top of or near the unit in such a way as to block the vents TECHNICAL AND SERVICE ASSISTANCE Technical and service assistance is available in North America between the hours of 8 00 a m and 5 00 p m Central Time by calling 800 369 7179 in Il...

Страница 4: ...eu of all other warranties No greater degree of liability is imposed on the manufacturer INSTALLATION AND OPERATING INSTRUCTIONS Please consult Appendix A for installation and operating instructions on the following models ABC360 91IND ABC750 91IND ABC1000 91IND ABC1500 91IND Please consult Appendix B for installation and operating instructions on the following models ABC500 91BUI ABC1000 91BUI AB...

Страница 5: ...time of order the power conditioner has been set during manufacture by the factory for a 480 volt input The input voltage of the power conditioner is selectable from 480 240 208 or 120 volts and may be changed by moving the jumpers on BOTH TB2 and TB3 See Figure 1 that follows for proper jumper positioning and an example of how the conditioner may be rewired When connections are completed replace ...

Страница 6: ...Figure 1 INDUSTRIAL POWER CONDITIONERS ...

Страница 7: ...pre configured by the factory for a 120 volt input Series 1 power conditioners are ordered for a specific input voltage and the circuit breaker installed in the unit is the correct one for the selected operating voltage The input voltage of both the GPI Series B and Series 1 can be set to 100 120 208 or 240 volts by changing jumpers on terminal block TB1 as shown in Figure 2 Series B power conditi...

Страница 8: ...013 25 H 5 00 JA2S A38 A 0005 25 H 15 25 JA2S A38 A 1525 25 H 5 50 JA2S A38 A 05R5 25 H 15 50 JA2S A38 A 1550 25 H 6 50 JA2S A38 A 06R5 25 H 17 00 JA2S A38 A 1700 25 H 7 75 JA2S A38 A 7R75 25 H 20 50 JA2S A38 A 2050 25 H 8 50 JA2S A38 A 08R5 25 H 25 50 JA2S A38 A 2550 25 H 8 75 JA2S A38 A 8R75 25 H 30 50 JA2S A38 A 3050 25 H 10 25 JA2S A38 A 1025 25 H OPERATING INSTRUCTIONS GPI Series B Complete a...

Страница 9: ...Figure 2 INPUT VOLTAGE ADJUSTMENT GPI SERIES B AND GPI SERIES 1 ABC500 XX ABC1000 XX ABC1500 XX ABC2000 XX ABC3000 XX ...

Страница 10: ...are accessed by removing the knockouts on the back panel Terminal blocks are designed to accept a maximum wire size of 8 AWG and 8 foot pounds of torque All applicable electrical codes must be observed for the installation of this device When wiring connections are complete replace the cover before applying power to the power conditioner OPERATING INSTRUCTIONS If power was turned off at the panel ...

Страница 11: ...input move circuit breaker lead from point E2 of the printed circuit filter assembly to point E3 To convert 240 volt input to 208 volt input move circuit breaker lead from point E3 of the printed circuit filter assembly to point E2 Factory default setting is 240 volt input unless specified differently at time of order with factory ...

Страница 12: ...on on models ending with suffix 2S only adjust taps on left side of transformer when viewed from rear of conditioner Moving taps permits changing of input operating voltage between 208 and 240 volts Input voltage adjustment taps this side of transformer ...

Страница 13: ...se SM503 RevC 11 23 04 2004 POWERVAR Inc In North America South America and the Caribbean 1450 Lakeside Drive Waukegan IL 60085 Phone 847 596 7000 Toll Free outside Illinois only 800 369 7179 Fax 847 596 7100 In EMEA Unit 5 Birch Kembrey Park Swindon Wiltshire SN2 8UU United Kingdom Phone 44 0 1793 553980 Fax 44 0 1793 535350 Access additional product information and support on the web at http www...

Отзывы: