background image

10

NT 874 717 A

ISOM HM420 plus RA720

Technical data HM420

Insulation coordination acc. to IEC 60664-1 / IEC 60664-3

Rated insulation voltage .......................................................................................................... 250 V
Rated impulse voltage/pollution degree ............................................................................ 4 kV / III
Protective separation (reinforced insulation) between ....................................................................

...............................................................................  (L1, L2, E, KE, 1, 2, 3, 4, Z, Z/k, I) - (11, 12, 14)

Voltage test according to IEC 61010-1  ................................................................................ 2.21 kV

Supply voltage

Supply voltage U

S

...................................................................................................................... = U

n

Power consumption ............................................................................................................... 

 4 VA

IT system being monitored

Nominal system voltage U

n

........................................................................................ AC 70...264 V

Nominal frequency f

n

 ....................................................................................................... 47...63 Hz

Insulation monitoring

Response value R

an

 ...................................................................................  50…500 k

Ω

 (50 k

Ω

)*

Relative percentage error  .....................................................................................................  ±10 %
Hysteresis..................................................................................................................................  25 %
Response time t

an

 at R

F

 = 0.5 x R

an

 and C

e

 = 0.5 μF  ............................................................. 

 5 s

Permissible system leakage capacitance C

e

 .............................................................................  5 μF

Measuring circuit

Measuring voltage U

...........................................................................................................  ±12 V

Measuring current I

m

 (at R

F

 = 0 

Ω

) ................................................................................... 

 50 μA

Internal DC resistance R

i

 ................................................................................................... 

 240 k

Ω

Impedance Z

i

, at 50 Hz ..................................................................................................... 

 200 k

Ω

Extraneous DC voltage U

fg

 .............................................................................................  

 DC 300 V

Load current monitoring

Response value, adjustable  ...................................................................................  5…50 A (7 A)*
Relative percentage error  .......................................................................................................  ±5 %
Hysteresis ..................................................................................................................................... 4%
Setting value load current measurement:
Transformer .....  3150 VA .......  4000 VA  ....... 5000 VA  ....... 6300 VA  ....... 8000 VA .....  10000 VA
I

alarm 1~

 ...................14 A .............. 18 A  .............  22 A  .............  28 A  .............. 35 A .............. 45 A

Temperature monitoring

Response value (fixed value)  ................................................................................................... 4 k

Ω

Release value (fixed value) .................................................................................................... 1.6 k

Ω

PTC thermistors acc. to DIN 44081 .......................................................................... max. 6 in series

Displays, memory

LC display ...................................................................................... multifunctional, not illuminated
Measured value insulation resistance ...................................................................  10 k

Ω

…1 M

Ω

Operating error  ...................................................................................................... ±10 %, ± 2 k

Ω

Measured value load current (as % of the set response value) ............................. 10 %…199 %
Operating error  ......................................................................................................... ±5 %, ±0.2 A
Password ................................................................................................. on, off / 0…999 (off, 0)*

Interface for RA720

Cable length, twisted pairs, shielded ................................................................................. 

 200 m

Recommended cable .......................  min. J-Y(St)Y 2x2 x 0.6; shield on one side connected to PE

Power supply (terminals 1 and 2):

V

s

 ..........................................................................................................................................  DC 24 V

I

max

 (max. 4 RA720) ..............................................................................................................  80 mA

Communication (terminal 3 and 4):

Interface/protocol ................................................... RS-485 / proprietary interface (no  bus ISOM)
Terminating resistor  ............................................................ 120 

Ω

 (0.25 W), internal, switchable

Interfaces for CT-HL765 measuring current transformer and 
temperature sensor

Cable lengths:
Single wire > 0.5 mm²  ..........................................................................................................  

 1 m

Single wire, twisted > 0.5 mm²  ..........................................................................................  

 10 m

twisted pair, shielded > 0.5 mm²  ....................................................................................... 

 40 m

Recommended cable ............................. min. J-Y(St)Y 2x0.6, shield on one side connected to PE

Caractéristiques techniques HM420

Coordination de l´isolement selon IEC 60664-1 / IEC 60664-3

Tension assignée .....................................................................................................................  250 V
Qualité diélectrique / degré de pollution ............................................................................ 4 kV / III
Séparation sûre (isolation renforcée) entre .......................................................................................
................................................................................ (L1, L2, E, KE, 1, 2, 3, 4, Z, Z/k, I) - (11, 12, 14)
Essai diélectrique selon IEC 61010-1  ................................................................................... 2,21 kV

Tension d´alimentation

Tension d´alimentation U

s

  ......................................................................................................  = U

n

Consommation propre ..........................................................................................................  

 4 VA

Réseau IT surveillé

Tension réseau U

n

 ....................................................................................................... AC 70...264 V

Fréquence nominale f

n

  ....................................................................................................  47...63 Hz

Surveillance de l´isolement

Valeur de seuil R

an

 ....................................................................................  50…500 k

Ω

 (50 k

Ω

)*

Tolérance du seuil ................................................................................................................. ±10 %
Hystérèse  .................................................................................................................................  25 %
Temps de réponse t

an

 pour R

F

 = 0,5 x R

an

 et C

e

 = 0,5 μF ....................................................... 

 5 s

Capacité de fuite C

e

 ....................................................................................................................  5 μF

Circuit de mesure

Tension de mesure U

m

  ..........................................................................................................  ±12 V

Courant de mesure I

m

 (pour R

F

 = 0 

Ω

) .............................................................................. 

 50 μA

Résistance interne DC R

i

 ...................................................................................................  

 240 k

Ω

Impédance Z

i

 pour 50 Hz .................................................................................................  

 200 k

Ω

Tension DC maxi étrangère U

fg

 .....................................................................................  

 DC 300 V

Surveillance du courant de charge

Valeur de seuil paramétrable ................................................................................. 5…50 A (7 A)*
Tolérance du seuil .................................................................................................................. ± 5 %
Hystérèse.....................................................................................................................................  4 %
Valeurs de réglage mesure du courant de charge :
Transformateur  3150 VA .......  4000 VA .......  5000 VA ........ 6300 VA  ....... 8000 VA ..... 10000 VA
I

alarm 1~

  .................. 14 A .............. 18 A .............. 22 A ..............  28 A  .............  35 A  .............  45 A

Surveillance de la température

Valeur de seuil (valeur fixe) .....................................................................................................  4 k

Ω

Valeur de relâchement (valeur fixe) .....................................................................................  1,6 k

Ω

Sonde selon DIN 44081 ............................................................................................. max. 6 en série

Affichage, mémoire

Affichage écran à cristaux liquides, multi fonctions, non rétroéclairé
Valeur mesurée résistance d´d´isolement ............................................................  10 k

Ω

…1 M

Ω

Erreur maximale de fonctionnement  ................................................................... ± 10 %, ± 2 k

Ω

Valeur mesurée courant de charge (en % de la valeur de seuil préréglée) ........... 10 %…199 %
Erreur maximale de fonctionnement  ..................................................................... ± 5 %, ± 0,2 A
Mot de passe ..........................................................................................  on, off / 0…999 (off, 0)*

interface pour le RA720

Longueur du câble, torsadé par paire, blindé  .................................................................... 

 200 m

Câble recommandé .......................................................... min. J-Y(St)Y 2x2 x 0,6; blindage sur PE

Alimentation (borne1 et 2) :

V

s

 ..........................................................................................................................................  DC 24 V

I

max

 (max. 4  RA720) ..............................................................................................................  80 mA

Communication (bornes 3 et 4) :

Interface / protocole .......................................................... RS-485 / propriétaire, pas de bus ISOM
Résistance terminale ......................................................... 120 

Ω

 (0,25 W), interne, commutable

Interfaces pour tore de détection CT-HL765 et sonde de 
température

Longueurs du câble :
unifilaire > 0,5 mm² ............................................................................................................... 

 1 m

unifilaire, torsadé> 0,5 mm²  ............................................................................................... 

 10 m

torsadé par paire, blindé > 0,5 mm² ................................................................................... 

 40 m

Câble recommandé ...............................................................  min. J-Y(St)Y 2x0,6; blindage sur PE

Summary of Contents for 4720 1812

Page 1: ...ment doit être branché par réseau ou circuit IT Lors de certains contrôles déconnecter les appareils du réseau avant tout essai d isolement ou test diélectrique Insulation monitoring device and control panel Intended use The ISOM HM420 monitors the insulation resistance RF in medical IT systems of AC 70 264 V In addition the IT system transform er s load current and temperature are monitored The d...

Page 2: ...ysfonctionnement HM420 En cas de dysfonctionnement le relais K1 11 12 14 commute et les 3 LED clignotent L écran affiche un code d erreur E01 raccord PE défectueux pas de liaison entre E et KE E03 rupture TI de mesure E04 court circuit TI de mesure E05 Exx défaut interne contactez notre service technique Protection par mot de passe HM420 Si le mode de protection par mot de passe a été activé on de...

Page 3: ...n off if the device is connected at the end of the bus 11 12 14 Alarm relay K1 Dimensions Schéma de branchement Connectez l appareil selon le schéma de branchement Les branchements sur KE et E doivent être effectués séparément Borne Raccordements E KE Connexion séparée de E et KE au PE L1 L2 Raccord au réseau IT à surveiller Tension d alimentation US cf plaque signalétique via un fusible 2 A gG Z ...

Page 4: ...us de la valeur de seuil Ran LED Alarm 2 est allumée jaune Valeur de seuil I et C dépassées AL1 AL2 LED Alarm 1 lights yellow Measured value has fallen below the res ponse value Ran LED Alarm 2 lights yellow Response value I and C exceeded 189 kΩ Ecran en mode standard Point clignotant fréquence de mesure Résistance d isolement RF 189 kΩ 189 kΩ Display in standard mode Flashing point measuring pul...

Page 5: ...s Les touches fléchées haut bas permettent de commuter entre la valeur d isolement et le courant de charge exprimé en pourcentage Si après la commutation la touche Enter est activée la mesure affichée est maintenue Signalisation d alarme Exemples d affichage des cinq types possibles d alarmes Si des alarmes différentes se produisent simultanément l affichage change toutes les 3 secondes Commande d...

Page 6: ...monitoring response value I Afficher et paramétrer la valeur de seuil de la surveillance du courant de charge en A I Query and setting the load current monitoring response value A 1 Sélectionner le mode de travail courant de travail ou courant de repos pour K1 1 Select N O or N C operation for K1 Su b Accès au sous menu et retour du sous menu Su b Access to the submenu and return from the sub menu...

Page 7: ... suivantes ces segments actifs sont représentés par un ovale Pour accéder au mode menu maintenez la touche MENU enfoncée pendant 2 s 50 2 s 2 s MENU 2 s 2 s MENU 1 x 2 s 2 s MENU 2 x Parameter settings An example is given below on how to change the alarm response value Ran R Proceed as follows 1 Keep the MENU Enter key pressed for 2 seconds The flashing short symbol R appears on the display 2 Conf...

Page 8: ... la fonction de protection par mot de passe b Modifier le mot de passe c Désactiver la fonction de protection par mot de passe 2 s MENU 2x 2 s 3 x 2 s MENU 2x 2 s 3 x 2 s MENU 3 x 2x 2 s Password protection Use this menu to activate the password protection to change the password or to deactivate the password protection The password can only be changed when the password protec tion has been activat...

Page 9: ...ue le cycle de programmation est terminé vous pouvez sélectionner des segments individuels de données à l aide des touches fléchées haut bas 2 s MENU 3 x 1 x 2x 2 s 2 s MENU 3 x 2 x 2 s MENU 3 x 3 x 3x 2 s Deactivating the CT monitoring function Resetting the device to its factory settings Device information query Use this menu to query the software version 1 xx After activat ing this function dat...

Page 10: ...ir shielded 0 5 mm 40 m Recommended cable min J Y St Y 2x0 6 shield on one side connected to PE Caractéristiques techniques HM420 Coordination de l isolement selon IEC 60664 1 IEC 60664 3 Tension assignée 250 V Qualité diélectrique degré de pollution 4 kV III Séparation sûre isolation renforcée entre L1 L2 E KE 1 2 3 4 Z Z k I 11 12 14 Essai diélectrique selon IEC 61010 1 2 21 kV Tension d aliment...

Page 11: ...nsport IEC 60721 3 2 2M2 Storage IEC 60721 3 1 1M3 Nombre et type Nombre 1 inverseur Mode de travail courant de repos courant de travail courant de repos Durée de vie électrique sous des conditions assignées de fonctionnement 10 000 manoeuvres Données des contacts selon IEC 60947 5 1 Catégorie d utilisation AC 13 AC 14 DC 12 DC 12 DC 12 Tension assignée de service 230 V 230V 24V 110V 220 V Courant...

Page 12: ... 66 mm Weight including mounting frame 80 g Ordering details Type Supply voltage Us Un Art No HM420 AC 70 264 V 42 460 Hz 4727 4723 RA720 DC 18 28 V 4720 1812 Absolute values of the voltage range CT HL765 Measuring current transformer 4765 0001 Temperature sensor CTP HL765 4765 0003 HM420 mounting frame 4700 6667 Schéma de branchement Mode de raccordement borniers à vis Section des raccordements r...

Reviews: