QuickServer Start-Up Guide
Page 70 of 71
Appendix D.5. Specifications
4
FS-QS-12X0-XXXX/ FS-QS-1X50-XXXX
5
FS-QS-1011-XXXX/FS-QS-12X1-XXXX/
FS-QS-1X51-XXXX
5
Available Ports
6-pin Phoenix connector: RS-485 or
RS-232 or RS-422 +/- ground port,
power +/- frame ground port
3-pin RS-485 Phoenix connector:
RS-485 +/- ground port
Ethernet-10/100 port
6-pin Phoenix connector: RS-485 or RS-232
or RS-422 +/- ground port,
power +/- frame ground port
2-pin FTT-10 LonWorks port
Ethernet-10/100 port
Power Requirements
Input Voltage:
9-30VDC or 12-24VAC
Input Power Frequency:
50/60 Hz.
Power Rating:
2.5 Watts
Current Draw:
@ 12V, 150 mA
Input Voltage:
9-30VDC or 12-24VAC
Input Power Frequency:
50/60 Hz.
Power Rating:
2.5 Watts
Current Draw:
@ 12V, 279 mA
Approvals
UL 916 approved
RoHS3 compliant
FCC part 15 compliant
DNP compliant
CE certified
BTL certified
WEEE compliant
UL 916 approved, RoHS compliant, FCC part
15 compliant, DNP compliant, LonMark
certification, WEEE compliant
SPID: 80:00:95:46:00:84:04:01
Profiles:
0000 - Node object (1)
0001 - Open Loop Sensor Object (5)
0003 - Open Loop Actuator Object (5)
Physical Dimensions
6
5.05
x 2.91 x 1.6 in. (12.82 x 7.39 x 4.06 cm)
Weight
0.4 lbs (0.2 Kg)
Operating Temperature
-40°C to 75°C (-40°F to167°F)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity
5 - 90% RH
(non-condensing)
Figure 45: Specifications
“This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
•
This device may not cause harmful interference
•
This device must accept any interference received, including interference that may cause
undesired operation.
NOTE:
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his expense. Modifications not expressly approved by FieldServer
could void the user's authority to operate the equipment
under FCC rules.”
4
Specifications subject to change without notice.
5
XXXX at the end of the part number identifies the code for the specific drivers included in the QuickServer. (
Appendix D.2
)
6
(WxDxH); Excluding mounting tabs.