background image

 

QuickServer Start-Up Guide 

Page 47 of 71 

Temp_Ret_2       

AI 11 

30021-30022 

Temp_Ret_3       

AI 12 

30023-30024 

Power_W_1        

AI 13 

30025-30026 

Power_W_2        

AI 14 

30027-30028 

Power_W_3        

AI 15 

30029-30030 

Vol_Flo_L_H_1    

AI 16 

30031-30032 

Vol_Flo_L_H_2    

AI 17 

30033-30034 

Vol_Flo_L_H_3    

AI 18 

30035-30036 

Volume_1         

AI 19 

30037-30038 

Volume_2         

AI 20 

30039-30040 

Volume_3         

AI 21 

30041-30042 

Enregy_MWH_1      AI 22 

30043-30044 

Enregy_MWH_2      AI 23 

30045-30046 

Enregy_MWH_3      AI 24 

30047-30048 

 

Appendix B.15. SensusHRI-B1-8Profile 
Mappings to BACnet and Modbus                   

Point Name 

BACnet 

Modbus 

Volume_1                        

AI 1 

30001-30002 

Meter_ID_1                      

AI 2 

30003-30004 

 

Appendix B.16. KromSchroderTRZ2S1 
Mappings to BACnet and Modbus                   

Point Name 

BACnet 

Modbus 

Volume_1                        

AI 1 

30001-30002 

Meter_ID_1                      

AI 2 

30003-30004 

 

Appendix B.17. KromSchroderDE10R25-
40B Mappings to BACnet and Modbus  

Point Name 

BACnet 

Modbus 

Dur_Avg_S_1                     

AI 001 

30001-30002 

Dur_Avg_S_2                     

AI 002 

30003-30004 

Dur_Avg_S_3                     

AI 003 

30005-30006 

Dur_Avg_S_4                     

AI 004 

30007-30008 

Dur_Avg_S_5                     

AI 005 

30009-30010 

Dur_Avg_S_6                     

AI 006 

30011-30012 

Dur_Avg_S_7                     

AI 007 

30013-30014 

Dur_Avg_S_8                     

AI 008 

30015-30016 

Dur_Avg_S_9                     

AI 009 

30017-30018 

Dur_Avg_S_10                    

AI 010 

30019-30020 

Dur_Avg_M_1                     

AI 011 

30021-30022 

Dur_Avg_M_2                     

AI 012 

30023-30024 

Dur_Avg_M_3                     

AI 013 

30025-30026 

Dur_Avg_M_4                     

AI 014 

30027-30028 

Dur_Avg_M_5                     

AI 015 

30029-30030 

Dur_Avg_M_6                     

AI 016 

30031-30032 

Dur_Avg_M_7                     

AI 017 

30033-30034 

Dur_Avg_M_8                     

AI 018 

30035-30036 

Dur_Avg_M_9                     

AI 019 

30037-30038 

Dur_Avg_M_10                    

AI 020 

30039-30040 

Dur_Avg_H_1                     

AI 021 

30041-30042 

Dur_Avg_H_2                     

AI 022 

30043-30044 

Dur_Avg_H_3                     

AI 023 

30045-30046 

Dur_Avg_H_4                     

AI 024 

30047-30048 

Dur_Avg_H_5                     

AI 025 

30049-30050 

Dur_Avg_H_6                     

AI 026 

30051-30052 

Dur_Avg_H_7                     

AI 027 

30053-30054 

Dur_Avg_H_8                     

AI 028 

30055-30056 

Dur_Avg_H_9                     

AI 029 

30057-30058 

Dur_Avg_H_10                    

AI 030 

30059-30060 

Dur_Avg_D_1                     

AI 031 

30061-30062 

Dur_Avg_D_2                     

AI 032 

30063-30064 

Dur_Avg_D_3                     

AI 033 

30065-30066 

Dur_Avg_D_4                     

AI 034 

30067-30068 

Dur_Avg_D_5                     

AI 035 

30069-30070 

Dur_Avg_D_6                     

AI 036 

30071-30072 

Dur_Avg_D_7                     

AI 037 

30073-30074 

Dur_Avg_D_8                     

AI 038 

30075-30076 

Dur_Avg_D_9                     

AI 039 

30077-30078 

Dur_Avg_D_10                    

AI 040 

30079-30080 

Dur_Act_Sec_1                   

AI 041 

30081-30082 

Dur_Act_Sec_2                   

AI 042 

30083-30084 

Dur_Act_Sec_3                   

AI 043 

30085-30086 

Dur_Act_Sec_4                   

AI 044 

30087-30088 

Dur_Act_Sec_5                   

AI 045 

30089-30090 

Dur_Act_Sec_6                   

AI 046 

30091-30092 

Dur_Act_Sec_7                   

AI 047 

30093-30094 

Dur_Act_Sec_8                   

AI 048 

30095-30096 

Dur_Act_Sec_9                   

AI 049 

30097-30098 

Dur_Act_Sec_10                  

AI 050 

30099-30100 

Dur_Act_Min_1                   

AI 051 

30101-30102 

Dur_Act_Min_2                   

AI 052 

30103-30104 

Dur_Act_Min_3                   

AI 053 

30105-30106 

Dur_Act_Min_4                   

AI 054 

30107-30108 

Dur_Act_Min_5                   

AI 055 

30109-30110 

Dur_Act_Min_6                   

AI 056 

30111-30112 

Dur_Act_Min_7                   

AI 057 

30113-30114 

Dur_Act_Min_8                   

AI 058 

30115-30116 

Dur_Act_Min_9                   

AI 059 

30117-30118 

Dur_Act_Min_10                  

AI 060 

30119-30120 

Dur_Act_Hrs_1                   

AI 061 

30121-30122 

Dur_Act_Hrs_2                   

AI 062 

30123-30124 

Dur_Act_Hrs_3                   

AI 063 

30125-30126 

Dur_Act_Hrs_4                   

AI 064 

30127-30128 

Dur_Act_Hrs_5                   

AI 065 

30129-30130 

Dur_Act_Hrs_6                   

AI 066 

30131-30132 

Dur_Act_Hrs_7                   

AI 067 

30133-30134 

Dur_Act_Hrs_8                   

AI 068 

30135-30136 

Dur_Act_Hrs_9                   

AI 069 

30137-30138 

Dur_Act_Hrs_10                  

AI 070 

30139-30140 

Dur_Act_Day_1                   

AI 071 

30141-30142 

Dur_Act_Day_2                   

AI 072 

30143-30144 

Dur_Act_Day_3                   

AI 073 

30145-30146 

Dur_Act_Day_4                   

AI 074 

30147-30148 

Dur_Act_Day_5                   

AI 075 

30149-30150 

Dur_Act_Day_6                   

AI 076 

30151-30152 

Dur_Act_Day_7                   

AI 077 

30153-30154 

Dur_Act_Day_8                   

AI 078 

30155-30156 

Dur_Act_Day_9                   

AI 079 

30157-30158 

Dur_Act_Day_10                  

AI 080 

30159-30160 

Energy_T_WH_1                   

AI 081 

30161-30162 

Energy_T_WH_2                   

AI 082 

30163-30164 

Energy_T_WH_3                   

AI 083 

30165-30166 

Energy_T_WH_4                   

AI 084 

30167-30168 

Energy_T_WH_5                   

AI 085 

30169-30170 

Energy_T_WH_6                   

AI 086 

30171-30172 

Energy_T_WH_7                   

AI 087 

30173-30174 

Energy_T_WH_8                   

AI 088 

30175-30176 

Energy_T_WH_9                   

AI 089 

30177-30178 

Energy_T_WH_10                  

AI 090 

30179-30180 

Energy_T_J_1                    

AI 091 

30181-30182 

Energy_T_J_2                    

AI 092 

30183-30184 

Energy_T_J_3                    

AI 093 

30185-30186 

Energy_T_J_4                    

AI 094 

30187-30188 

Energy_T_J_5                    

AI 095 

30189-30190 

Energy_T_J_6                    

AI 096 

30191-30192 

Summary of Contents for FieldServer FS-QS-1 0 Series

Page 1: ...Document Revision 2 J T18600 FieldServer QuickServer Start up Guide FS QS 1011 12X0 12X1 1X50 1X51 APPLICABILITY EFFECTIVITY Effective for all systems manufactured after July 2020...

Page 2: ...ical support needs related to the FieldServer product MSA Safety 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email smc suppor...

Page 3: ...e 21 6 2 Connect the PC to the QuickServer Over the Ethernet Port 21 6 3 Connecting to the QuickServer 22 6 3 1 Using the FieldServer Toolbox to Discover and Connect to the QuickServer 22 6 3 2 Using...

Page 4: ...UF 280T Mappings to BACnet and Modbus 46 Appendix B 15 SensusHRI B1 8Profile Mappings to BACnet and Modbus 47 Appendix B 16 KromSchroderTRZ2S1 Mappings to BACnet and Modbus 47 Appendix B 17 KromSchrod...

Page 5: ...2 Change FieldServer Password 66 Appendix D Reference 67 Appendix D 1 LED Functions 67 Appendix D 2 QuickServer FS QS 101X DCC 68 Appendix D 3 QuickServer 1XXX Part Numbers 68 Appendix D 4 Compliance...

Page 6: ...19 Warning Expanded Text 24 Figure 20 FieldServer Login 24 Figure 21 Security Mode Selection Screen 25 Figure 22 Security Mode Selection Screen 26 Figure 23 FS GUI Landing Page 27 Figure 24 FS GUI Ne...

Page 7: ...lected drivers on the FS QS 1X11 and FS QS 12X1 one of those drivers is LonWorks A sample configuration file is also pre loaded onto the QuickServer All instruction manuals driver manuals support util...

Page 8: ...mation about the BACnet Testing Laboratory Click here for the BACnet PIC Statement LonMark International is the recognized authority for certification education and promotion of interoperability stand...

Page 9: ...S 8915 35 QS WARNING Install only as instructed failure to follow the installation guidelines or using screws without the DIN rail mounting bracket could result in permanent damage to the product If t...

Page 10: ...QuickServer Start Up Guide Page 10 of 71 4 2 Dimensions 4 2 1 Dimension Drawing FS QS 1X10 XXXX R1 Port R2 Port Figure 2 FS QS 1X10 XXXX...

Page 11: ...QuickServer Start Up Guide Page 11 of 71 4 2 2 Dimension Drawing FS QS 1XX1 XXXX LonWorks Port R2 Port Figure 3 FS QS 1XX1 XXXX...

Page 12: ...QuickServer Start Up Guide Page 12 of 71 4 2 3 Dimension Drawing FS QS 123X Models with RS 422 R1 Port R2 Port Figure 4 FS QS 123X models with RS 422...

Page 13: ...t false bits of data from being detected The bias resistors typically pull one line high and the other low far away from the decision point of the logic In the RS 485 carrier the bias resistor is 510...

Page 14: ...ation Resistor Termination resistors are also used to reduce noise These pull the two lines of an idle bus together However they would override the effect of any bias resistors if connected Terminatio...

Page 15: ...ther power supply requirements Position A The Carrier makes use of a full wave rectifying bridge Can be used for 12 24VAC input or 9 30VDC input At 9VDC this becomes marginal Position B The Carrier ma...

Page 16: ...er NOTE The following only applies to models FS QS 1A50 FS QS 1A51 FS QS 1B51 FS QS 1B51 FS QS 1C51 and FS QS 1C51 The Master Slave jumper is used to set the M Bus hardware as a Master or Slave device...

Page 17: ...ced below o The default factory setting is OFF switch position right side o To enable biasing turn the bias switch ON switch position left side NOTE Biasing only needs to be enabled on one device The...

Page 18: ...200 38400 57600 115200 For connection details to RS 232 or RS 422 refer to Appendix A 1 5 1 2 RS 485 Connection R1 Port NOTE The following only applies to non LonWorks QuickServers with an RS 435 R1 p...

Page 19: ...sure to access the Service Pin See the instructions on the QuickServer as to which way to toggle the screwdriver during commissioning 5 3 QuickServer KNX FS QS 124X XXXX Connect the QuickServer to the...

Page 20: ...Connection R2 Port only available on FS QS 122X Models Refer to Appendix A2 for further hardware connection options The following Baud Rates are supported on the R2 Port 4800 9600 19200 38400 57600 1...

Page 21: ...D terminal The QuickServer is factory set for 9 30V DC or 12 24V AC 6 2 Connect the PC to the QuickServer Over the Ethernet Port Connect an Ethernet cable between the PC and QuickServer or connect the...

Page 22: ...ckServer and launch the FS GUI NOTE If the connect button is greyed out the QuickServer s IP Address must be set to be on the same network as the PC Section 8 1 6 3 2 Using a Web Browser to Connect to...

Page 23: ...rusted This will cause the following pop up windows to appear When the Web Server Security Unconfigured window appears read the text and choose whether to move forward with HTTPS or HTTP When the warn...

Page 24: ...default is admin and the Password found on the label of the FieldServer NOTE There is also a QR code in the top right corner of the FieldServer label that shows the default unique password when scann...

Page 25: ...l appear that allows the user to select which mode the FieldServer should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Appendix C...

Page 26: ...ivate Key text into their respective fields If the Private Key is encrypted type in the associated Passphrase Click Save A Redirecting message will appear After a short time the Web Configurator page...

Page 27: ...tton see Figure 23 allows users to connect to the SMC Cloud MSA Safety s device cloud solution for IIoT The SMC Cloud enables secure remote connection to field devices through a FieldServer and its lo...

Page 28: ...w Subnet Mask If necessary change the IP Gateway Default Gateway field Type in a new IP Gateway NOTE If the FieldServer is connected to a router the IP Gateway of the FieldServer should be set to the...

Page 29: ...gisters in the Config csv file for the initial start up If not the product is shipped with a sample config csv that shows an example of the drivers ordered In the main menu of the FS GUI screen go to...

Page 30: ...hen File Transfer and finally Update Browse and select the csv file open then click Submit Once download is complete a message bar will appear confirming that the configuration was updated successfull...

Page 31: ...menu of the FS GUI screen click Setup then File Transfer Click the config csv link under the Retrieve heading in the middle section of the screen o The file will automatically download to the web bro...

Page 32: ...the number of messages on each protocol 8 5 1 Accessing SMC Cloud The SMC Cloud button see Figure 23 allows users to connect to the SMC Cloud MSA Safety s device cloud solution for IIoT The SMC Cloud...

Page 33: ...r to peer high speed communication when low bus latency is required very few devices on the bus Its usage is very specific to client installations requirements NOTE The RS 232 looks similar to the RS...

Page 34: ...ignals may be crossed Pin 5 SHD Shield connection must be connected on at least one side of the bus but not necessarily on both sides POWER Connector Please note that AC voltage is not supported on th...

Page 35: ...arms etc This allows BMS systems to access a KNX network using direct read and write or with KNX configured groups This setup does not require the use of ETS4 to configure the QuickServer KNX gateway...

Page 36: ...kServer Gateway is configurable to act as both a Master and a Slave M Bus device The M Bus Connector consist of a and terminal Most M Bus Devices are not polarity sensitive although the polarity of th...

Page 37: ...secure Modbus TCP connection on port 1502 Appendix A 4 1 1 Simple Secure Server Configuration Add TLS_Port parameter in the connections section of the configuration file and set to a port number betwe...

Page 38: ...er with the following connection settings Connections Adapter Protocol TLS_Port Validate_Client_Cert Cert_Authority_File N1 Modbus TCP 1502 Yes my_authorized_clients pem This configuration has the Fie...

Page 39: ...ymously known as common name host name or domain etc The common name can be obtained by the following methods Ask the certificate issuer for the host name Use online tools to decode the certificate fo...

Page 40: ...rtificate against its own internal authority file before finalizing the connection By default this means the FieldServer will only establish connections to other FieldServers Remote_Node_TLS_Port Vali...

Page 41: ...5 30016 RH_Avg AI 09 30017 30018 Appendix B 4 EMU 3PH Power 3 85 Mappings to BACnet and Modbus Point Name BACnet Modbus MBUS_Meter_ node_id_Alarms AI 01 30001 30002 Energy_WH_1 AI 02 30003 30004 Energ...

Page 42: ...Vol_Flo_L_H_1 AI 36 30071 30072 Vol_Flo_L_H_2 AI 37 30073 30074 Vol_Flo_L_H_3 AI 38 30075 30076 Vol_Flo_L_H_4 AI 39 30077 30078 Vol_Flo_L_H_5 AI 40 30079 30080 Vol_Flo_L_H_6 AI 41 30081 30082 Vol_Flo...

Page 43: ...Avg_M_4 AI 14 30027 30028 Dur_Avg_M_5 AI 15 30029 30030 Dur_Avg_M_6 AI 16 30031 30032 Dur_Avg_M_7 AI 17 30033 30034 Dur_Avg_M_8 AI 18 30035 30036 Dur_Avg_M_9 AI 19 30037 30038 Dur_Avg_M_10 AI 20 30039...

Page 44: ...AI 142 30283 30284 Temp_Ret_3 AI 143 30285 30286 Temp_Ret_4 AI 144 30287 30288 Temp_Ret_5 AI 145 30289 30290 Temp_Ret_6 AI 146 30291 30292 Temp_Ret_7 AI 147 30293 30294 Temp_Ret_8 AI 148 30295 30296 T...

Page 45: ...Pressure_9 AI 279 30557 30558 Pressure_10 AI 280 30559 30560 Mass_1 AI 281 30561 30562 Mass_2 AI 282 30563 30564 Mass_3 AI 283 30565 30566 Mass_4 AI 284 30567 30568 Mass_5 AI 285 30569 30570 Mass_6 A...

Page 46: ...0818 Alarm_Flags_10 AI 410 30819 30820 Appendix B 12 Kamstrup 66 Mappings to BACnet and Modbus Point Name BACnet Modbus Energy_T_WH_1 AI 01 30001 30002 Energy_T_WH_2 AI 02 30003 30004 Energy_T_WH_3 AI...

Page 47: ..._Avg_D_4 AI 034 30067 30068 Dur_Avg_D_5 AI 035 30069 30070 Dur_Avg_D_6 AI 036 30071 30072 Dur_Avg_D_7 AI 037 30073 30074 Dur_Avg_D_8 AI 038 30075 30076 Dur_Avg_D_9 AI 039 30077 30078 Dur_Avg_D_10 AI 0...

Page 48: ...6 Time_Sec_4 AI 164 30327 30328 Time_Sec_5 AI 165 30329 30330 Time_Sec_6 AI 166 30331 30332 Time_Sec_7 AI 167 30333 30334 Time_Sec_8 AI 168 30335 30336 Time_Sec_9 AI 169 30337 30338 Time_Sec_10 AI 170...

Page 49: ...ol_Flo_L_M_1 AI 301 30601 30602 Vol_Flo_L_M_2 AI 302 30603 30604 Vol_Flo_L_M_3 AI 303 30605 30606 Vol_Flo_L_M_4 AI 304 30607 30608 Vol_Flo_L_M_5 AI 305 30609 30610 Vol_Flo_L_M_6 AI 306 30611 30612 Vol...

Page 50: ...re 1 AI 16 30031 30032 Flow Temperature 2 AI 17 30033 30034 Flow Temperature 3 AI 18 30035 30036 Return Temperature 1 AI 19 30037 30038 Return Temperature 2 AI 20 30039 30040 Return Temperature 3 AI 2...

Page 51: ...0177 30178 Fabrication Number 1 AI 90 30179 30180 Fabrication Number 2 AI 91 30181 30182 Fabrication Number 3 AI 92 30183 30184 Appendix B 23 Kamstrup Multical Mappings to BACnet and Modbus Point Name...

Page 52: ...3 30134 Volume Flow 6 AI 68 30135 30136 Volume Flow 7 AI 69 30137 30138 Volume Flow 8 AI 70 30139 30140 Volume Flow 9 AI 71 30141 30142 Volume 1 AI 72 30143 30144 Volume 2 AI 73 30145 30146 Volume 3 A...

Page 53: ...stom_1 AI 5 30009 30010 Power_W_1 AI 6 30011 30012 Pressure_1 AI 7 30013 30014 Mass_1 AI 8 30015 30016 Vol_Flo_L_M_1 AI 9 30017 30018 Volume_1 AI 10 30019 30020 Unknown_1 AI 11 30021 30022 Unknown_2 A...

Page 54: ...Dif_3 AI 19 30037 30038 Time_Op_Hrs_1 AI 20 30039 30040 Time_Op_Hrs_2 AI 21 30041 30042 Time_Op_Hrs_3 AI 22 30043 30044 Power_W_1 AI 23 30045 30046 Power_W_2 AI 24 30047 30048 Power_W_3 AI 25 30049 30...

Page 55: ...in the PC s Device Manager List and that it is configured to run the TCP IP protocol Check that the IP netmask of the PC matches the QuickServer The Default IP Address of the QuickServer is 192 168 2...

Page 56: ...FieldServer Diagnostics page via one of the following methods o Open the FieldServer FS GUI page and click on Diagnostics in the Navigation panel o Open the FieldServer Toolbox software and click the...

Page 57: ...e diagnosis of the problem NOTE While all necessary documentation is shipped with the FieldServer on the USB flash drive these documents are constantly being updated Newer versions may be available on...

Page 58: ...ck on the Start Diagnostic button o Wait for the capture period to finish and the Diagnostic Test Complete window will appear Step 2 Send Log o Once the diagnostic test is complete a zip file is saved...

Page 59: ...ev 3 and higher NOTE Internet Explorer is no longer supported as recommended by Microsoft NOTE Computer and network firewalls must be opened for Port 80 to allow FieldServer GUI to function Appendix C...

Page 60: ...pendix C 4 1 Change Security Mode Click Security in the Navigation panel Click the Mode desired o If HTTPS with own trusted TLS certificate is selected follow instructions in Section 7 2 1 Click the S...

Page 61: ...will only be available if the security mode was previously setup as HTTPS with own trusted TLS certificate Click Security in the Navigation panel Click the Edit Certificate button to open the certific...

Page 62: ...the FieldServer Recovery Instructions document For QuickServer 2xx0 ProtoNode FPC N54 or ProtoAir recovery instructions see the FieldServer Next Gen Recovery document If the default unique password i...

Page 63: ...up and Password o User details are hashed and salted NOTE The password must meet the minimum complexity requirements An algorithm automatically checks the password entered and notes the level of stren...

Page 64: ...Click the pencil icon next to the desired user to open the User Edit window Once the User Edit window opens change the User Security Group and Password as needed Click Confirm Once the Success messag...

Page 65: ...Guide Page 65 of 71 Appendix C 5 1 3 Delete Users Click the trash can icon next to the desired user to delete the entry When the warning message appears click Confirm Figure 41 Setup Users Figure 42...

Page 66: ...ents An algorithm automatically checks the password entered and notes the level of strength on the top right of the Password text field NOTE If a gateway in the field is updated to a secure gateway th...

Page 67: ...starts flashing During the first 20 seconds the LED should be off ERR The ERR LED will go on solid 15 seconds after power up It will turn off after 5 seconds A steady red light will indicate there is...

Page 68: ...JCI Metasys N2 0117 SNMP BACnet IP 1047 SNMP LonWorks 1178 SNMP JCI Metasys N2 1154 SNMP BACnet MS TP 1200 BACnet MS TP LonWorks 0345 Appendix D 3 QuickServer 1XXX Part Numbers Field Connections Inte...

Page 69: ...y with local electrical code o Be suited to the expected operating temperature range o Meet the current and voltage rating for QuickServer Net Furthermore the interconnecting power cable shall o Be of...

Page 70: ...to167 F Surge Suppression EN61000 4 2 ESD EN61000 4 3 EMC EN61000 4 4 EFT Humidity 5 90 RH non condensing Figure 45 Specifications This device complies with part 15 of the FCC Rules Operation is subj...

Page 71: ...hich original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage...

Reviews: