background image

How to Order

Series 

VP300/500/700

Rubber Seal

3 Port/Pilot Poppet Type

Body Ported/Single Unit

VP 3 4 2

5 G

1 01

A

Series

3
5
7

VP300
VP500
VP700

5
6

24 VDC
12 VDC

Pilot type

R

Internal pilot
External pilot

Bracket

F

Without bracket
With bracket

Thread type

F

N

T

Rc

G

NPT

NPTF

Light/surge voltage suppressor

DC

AC

S
Z
R
U

Without light/surge voltage suppressor
With surge voltage suppressor
With light/surge voltage suppressor
With surge voltage suppressor (Non-polar)
With light/surge voltage suppressor (Non-polar)

Port size

01
02
03
04

Symbol Port size

VP300

1/8
1/4
3/8
1/2

VP500 VP700

Manual override

—:

 Non-locking

push type

D

:

 Push-turn locking

slotted type

E

:

 Push-turn locking

lever type

Pressure specification

K

Standard (0.7 MPa)
High-pressure type (1.0 MPa)

Electrical entry

Grommet

Conduit

terminal

L-type plug

connector

M-type plug

connector

DIN

terminal

DIN

(EN175301-803)

terminal

G

: Lead wire

length 300 mm

H

: Lead wire

length 600 mm

L

: With lead wire

(length 300 mm)

LN

:

Without lead wire

LO

:

Without connector

M

: With lead wire

(length 300 mm)

D

: With connector

Y

: With connector

T

: Conduit 

terminal

DO

:

Without connector

YO

:

Without connector

MN

:

Without lead wire

MO

:

Without connector

G

: Lead wire

length 300 mm

H

: Lead wire

length 600 mm
DC
Without light/
surge voltage
suppressor

Coil specification

T

Standard
With power saving circuit (DC only)

Body ported

Note 1) Be sure to select the power sa-

ving circuit type when it is conti-
nuously energized for a long ti-
me.
(Refer to back page 7 for de-
tails.)

Note 2) T type is only available for DC 

mode. When T is selected, only 
Z type of light/surge voltage 
suppressor is available.
(Note that when the electrical 
entry of DIN terminal type wit-
hout connector is selected, only 
DOS and YOS are available.)

Note 1) There is no S option for AC mode, since a rectifier prevents 

surge voltage generation.

Note 2) In the DIN terminal type, since a light is installed in the con-

nector, DOZ, DOU, YOZ, YOU are not available.

Rated voltage

DC

1
2
3
4
7

100 VAC
200 VAC
110 VAC [115 VAC]
220 VAC [230 VAC]
240 VAC

AC (50/60 Hz)

When  using  the  surge  voltage  suppressor  type, 

residual  voltage  will  remain.  Refer  to  back  page  7 

for details.  

Caution

Note 1) LN and MN types are with 2 sockets.
Note 2) Refer to back page 4 when different length of lead wire for L/M-type plug connector is required.
Note 3) Refer to back page 5 for details on the DIN (EN175301-803) terminal.
Note 4) The AC mode of G, H, L and M types are not CE compliant.

[IP65 compatible] [IP65 compatible] [IP65 compatible]

Type of actuation

A
B

N.C. (Normally closed)
N.O. (Normally open)

Made to Order

X500

Pilot exhaust port with piping thread (M3) 
specification (Refer to page 24). 

Note) Only DIN and conduit terminal types 

are available for AC mode.
Refer to the electrical entry for details.

Note 1)

Note) Only DIN and conduit terminal 
types can be set for AC mode. Refer 
to the electrical entry for details.

Low power consumption 1.5 W (DC)
Possible to use as either a 

selector or divider valve
Possible to change from 

N.C. to N.O.

Possible to use in vacuum 

applications

Up to –100 kPa

Use  external  pilot  type  in  the  following 
cases:
• For  vacuum  or  for  low  pressure:  0.2  MPa 

or less.

• Please  consult  SMC  for  use  in  a  vacuum 

hold application.

• When having P port downsized in diameter
• When  using  A  port  as  the  atmospheric 

releasing port, e.g. air blower.

External Pilot

Specifications

Solenoid Specifications

Response Time

Electrical entry

Coil rated voltage (V)

Allowable voltage fluctuation

Power consumption (W)

Apparent power
(VA)

Note 1) 

Surge voltage suppressor
Indicator light

24, 12

100, 110, 200, 220, 240

±

10% of rated voltage

Diode (Non-polar type: Varistor)

LED (Neon bulb is used for AC mode of D, Y, T.)

1.5 (With light: 1.75)

0.75 (With light only)

1.55 (With light: 1.7)

1.5 (With light: 1.55)

0.55 (With light only)

1.55 (With light: 1.65)

Grommet (G), (H)

L-type plug connector (L)

M-type plug connector (M)

DIN terminal (D)

DIN (EN175301-803) terminal (Y)

Conduit terminal (T)

DC
AC (50/60 Hz)

Standard

With power saving circuit

100 V
110 V
[115 V]
200 V
220 V
[230 V]
240 V

G, H, L, M

D, Y, T

Note 1) 

It is in common between 110 VAC and 115 VAC, and between 220 VAC and 230 VAC.

Note 2) 

Allowable voltage fluctuation is –15% to +5% of the rated voltage for 115 VAC or 230 VAC.

Note 3) 

Since voltage drops due to the internal circuit in S, Z, T types (with power saving circuit), the 
allowable voltage fluctuation should be within the following range. 
24 VDC: –7% to +10%
12 VDC: –4% to +10%

Fluid
Type of actuation
Internal pilot
Operating pressure range (MPa)

External pilot
Operating pressure range (MPa)

Ambient and fluid temperature (

°

C)

Max. operating frequency (Hz)

Manual override

Pilot exhaust type
Lubrication
Mounting orientation
Impact/Vibration resistance (m/s

2

Note)

Enclosure

Standard
High-pressure type
Standard
High-pressure type
Pilot pressure range

Note) Impact resistance:  No malfunction occurred when it is tested in the axial direction and at the right 

angles to the main valve and armature in both energized and de-energized states 
every once for each condition. (Values at the initial period)

Vibration resistance: No malfunction occurred in a one-sweep test between 45 and 2000 Hz. Test was 

performed at both energized and de-energized states in the axial direction and at 
the right angles to the main valve and armature. (Values at the initial period)

VP342

VP542

VP742

Standard (0.2 to 0.7)
High-pressure type (0.2 to 1.0)
Standard (0.2 to 0.7)
High-pressure type (0.2 to 1.0)
Standard (0.2 to 0.7)
High-pressure type (0.2 to 1.0)

Response time ms (at 0.5 MPa)

13 or less
17 or less
14 or less
18 or less
19 or less
22 or less

Without light/surge 

voltage suppressor

With light/surge voltage suppressor

S, Z type

38 or less
42 or less
39 or less
43 or less
44 or less
47 or less

R, U type

16 or less
20 or less
17 or less
21 or less
22 or less
25 or less

AC

38 or less
42 or less
39 or less
43 or less
44 or less
47 or less

Note) Based on dynamic performance test, JIS B 8375-1981. (Coil temperature: 20

°

C, at rated voltage)

Pressure specifications

Model

DC

AC

Series VP300

Series VP500

Series VP700

Made to Order

(Refer to page 24 for details.)

Pilot exhaust port with piping 
thread (M3) specification

X500

Air

N.C. or N.O. (Convertible)

0.2 to 0.7
0.2 to 1.0

–100 kPa to 0.7
–100 kPa to 1.0

Same as operating pressure (Min. 0.2 MPa)

–10 to 50 (No freezing)

5

Individual exhaust

Not required

Unrestricted

300/50

Dust-tight (IP65 for D, Y, T)

Non-locking push type

Push-turn locking slotted type

Push-turn locking lever type

• Refer to back page 8 for 

changing the type of actuation. 

  

Series 

VP300/500/700

Pilot Poppet Type

Body Ported/Single Unit

2

Summary of Contents for VP300 Series

Page 1: ...ide Rubber material HNBR Ozone resistant specification The pilot valve poppet is made of FKM Strainer Electrical power waveform of energy saving type Applied voltage Standard With power saving circuit...

Page 2: ...O External pilot N C N O Port size Voltage Light surge voltage suppressor Manual override Electrical entry VP300 VP500 VP700 VP300 VP500 VP700 12 VDC 24 VDC 100 VAC 200 VAC 110 VAC 220 VAC 240 VAC P 1...

Page 3: ...s EXH port type 2 to 20 stations 2 to 20 stations 2 to 20 stations Common EXH Individual EXH Common EXH Individual EXH Common EXH Individual EXH VV3P3 41 VV3P3 42 VV3P5 41 VV3P5 42 VV3P7 41 VV3P7 42 M...

Page 4: ...PA500 VPA700 VPA300 VPA500 VPA700 P 25 P 30 1 8 1 4 1 4 3 8 3 8 1 2 1 8 1 4 1 4 3 8 3 8 1 2 4 2 8 9 15 3 3 8 8 8 15 0 Series VPA300 500 700 Model Selection by Operating Conditions e Air Operated Valve...

Page 5: ...stations VV3PA3 41 VV3PA3 42 VV3PA5 41 VV3PA5 42 VV3PA7 41 VV3PA7 42 VPA300 VPA500 VPA700 P 35 Note Supply pressure to 1 P ports and exhaust air from 3 R ports on both sides for 10 stations or more Co...

Page 6: ...uit DC only Body ported Note 1 Be sure to select the power sa ving circuit type when it is conti nuously energized for a long ti me Refer to back page 7 for de tails Note 2 T type is only available fo...

Page 7: ...cation Mounting orientation Impact Vibration resistance m s2 Note Enclosure Standard High pressure type Standard High pressure type Pilot pressure range Note Impact resistance No malfunction occurred...

Page 8: ...racket Note 2 These valves have been calculated according to ISO6358 and indicate the flow rate under standard conditions with an inlet pressure of 0 6 MPa relative pressure and a pressure drop of 0 1...

Page 9: ...a G H L LN LO M MN MO Grommet Lead wire length 300 mm Grommet Lead wire length 600 mm With lead wire Without lead wire Without connector With lead wire Without lead wire Without connector Electrical e...

Page 10: ...h 102 4 17 5 45 54 5 5 4 35 19 7 Indicator light Mounting groove for M5 thread 56 4 20 4 16 1 1 26 5 4 5 3 8 PE port Note 1 8 1 4 1 P 3 R port NO 3R 1P 20 9 Distance between ports Max 10 115 3 86 9 76...

Page 11: ...0 7 25 6 1 4 3 8 1 P 3 R port 3 8 PE port Note NO 1P 3R 31 5 Distance between ports 89 2 79 2 79 2 69 2 Max 10 131 5 Pg9 Indicator light Applicable cable O D 4 5 to 7 Note Refer to page 24 when piping...

Page 12: ...mounting 107 2 97 2 97 2 87 2 Max 10 154 5 Pg9 Indicator light Applicable cable O D 4 5 to 7 Note Refer to page 24 when piping to PE port is required 40 31 5 60 74 6 4 63 Indicator light Mounting groo...

Page 13: ...10 VAC 115 VAC 220 VAC 230 VAC 240 VAC AC 50 60 Hz When using the surge voltage suppressor type residual voltage will remain Refer to back page 7 for details Caution Note 1 LN and MN types are with 2...

Page 14: ...ctuation Internal pilot Operating pressure range MPa External pilot Operating pressure range MPa Ambient and fluid temperature C Max operating frequency Hz Manual override Pilot exhaust type Lubricati...

Page 15: ...3 15 0 0 24 0 14 0 20 0 13 0 24 0 17 0 8 0 9 1 7 2 0 3 1 3 4 216 149 211 149 370 245 362 245 676 459 658 459 252 185 247 185 406 281 398 281 712 495 694 495 Note 1 valves Values without sub plate Note...

Page 16: ...e 1 0 MPa G H L LN LO M MN MO Grommet Lead wire length 300 mm Grommet Lead wire length 600 mm With lead wire Without lead wire Without connector With lead wire Without lead wire Without connector Elec...

Page 17: ...ounting Manual override 2A NO 1P NC NC 18 5 12 1 8 1 4 3 R port 3R 43 7 18 5 Indicator light 110 9 100 9 100 9 90 9 Max 10 105 3 Pg9 Indicator light Applicable cable O D 4 5 to 7 X Note Refer to page...

Page 18: ...49 7 28 5 1 4 3 8 1 P port 1 8 External pilot port PE port Note 3 8 50 5 23 Indicator light 3R 23 13 5 1 4 3 8 3 R port Max 10 131 5 117 7 107 7 107 7 97 7 Pg9 Indicator light Applicable cable O D 4 5...

Page 19: ...nting Manual override X 80 64 40 32 5 21 16 95 5 PE port Note 4 1 8 External pilot port 3 8 1 2 1 P port 16 40 3 8 1 2 2 A port 3R 24 16 3 8 1 2 3 R port 72 5 24 Indicator light Note Refer to page 24...

Page 20: ...Applicable series 1 4 3 8 1 2 VP300 VP500 VP700 VV3P 3 3 42 04 02 Series 3 5 7 VP300 VP500 VP700 Thread type F N T Rc G NPT NPTF Stations 02 20 2 stations 20 stations Port size 02 03 04 Symbol Port s...

Page 21: ...C 220 VAC 230 VAC 240 VAC AC 50 60 Hz When using the surge voltage suppressor type residual voltage will remain Refer to back page 7 for details Caution Note 1 LN and MN types are with 2 sockets Note...

Page 22: ...ng 2 types of exhaust ports Common or individual exhaust type are available For individual exhaust type exhaust can be restricted Easy to change between N C and N O Type of actuation can be easily cha...

Page 23: ...4 104 4 Max 10 105 3 Pg9 Indicator light Applicable cable O D 4 5 to 7 3R 1P Note Refer to page 24 when piping to PE port is required Series VP300 Dimensions Type 41 Common exhaust VV3P3 41 1 02 Grom...

Page 24: ...30 5 24 50 13 5 17 5 M5 x 0 8 Common external pilot port External pilot specification R PE port Note 3 8 1 4 1 P port Note Refer to page 24 when piping to PE port is required Stationn L1 L2 2 83 5 68...

Page 25: ...ort Note 3 8 M5 x 0 8 Common external pilot port External pilot specification R 3 8 1 P 3 R port Note Refer to page 24 when piping to PE port is required Stationn L1 L2 2 95 80 128 113 161 146 194 179...

Page 26: ...O D 4 5 to 7 1P 1P 16 5 23 5 60 42 30 PE port Note 3 8 M5 x 0 8 Common external pilot port External pilot specification R 3 8 1 P port Note Refer to page 24 when piping to PE port is required L1 L2 9...

Page 27: ...L1 Approx 300 Lead wire length 145 3 106 8 51 5 145 3 106 8 51 5 N C N O Pitch P 41 Station 1 Station n Manual override 2 x 8 5 For mounting Stationn L1 L2 2 115 99 3 156 140 4 197 181 5 238 222 6 27...

Page 28: ...e length 145 3 106 8 51 5 145 3 106 8 51 5 2 x 8 5 For mounting N C N O Pitch P 41 Station 1 Station n Manual override Applicable cable O D 4 5 to 7 Applicable cable O D 4 5 to 7 Stationn L1 L2 2 115...

Page 29: ...pilot exhaust port PE port is available when the valve is used in an environment where the exhaust from the pilot valve is not allowable or intrusion of ambient dust should be prevented VP 4 3 5 7 2 4...

Page 30: ...ack page 8 for changing the type of actuation Note Impact resistance No malfunction occurred when tested in both the axial and right angle directions of main valve and armature tested in both energize...

Page 31: ...no VP300 227 1A VP500 227 1A VP700 227 1A Bracket With 2 screws Model VPA342 VPA542 VPA742 12 A 2 1 P 3 R Body Adapter plate End plate Piston Spool valve Retainer Spring No 1 2 3 4 5 6 7 Description M...

Page 32: ...16 5 54 5 45 5 4 35 1 8 12 PA port Mounting groove for M5 thread NO 3R 1P 3 53 7 26 5 4 5 16 20 4 M5 x 0 8 Breathing hole 1 8 1 4 1 P 3 R port 20 9 Distance between ports NO 3R 1P 3 53 7 26 5 4 5 16 2...

Page 33: ...vacuum VPA542V 1 F 02 03 A B 12 22 5 60 50 45 5 4 1 8 12 PA port Mounting groove for M5 thread 12 22 5 60 50 45 5 4 1 8 12 PA port Mounting groove for M5 thread 46 45 40 31 5 4 39 6 23 5 2 x 4 2 For...

Page 34: ...ing NO 3R 1P 3 100 8 42 30 5 40 9 3 8 1 2 1 P 3 R port M5 x 0 8 Breathing hole 43 Distance between ports Series VPA700 Body Ported Dimensions Standard VPA742 1 F 03 04 A B For vacuum VPA742V 1 F 03 04...

Page 35: ...n resistance No malfunction occurred when tested in a one sweep test between 45 and 2000 Hz in both the axial and right angle directions of main valve and armature tested Specifications Flow Character...

Page 36: ...P344 VP300 217 1 VP300 202 VP300 224 1 M3 x 36 Gasket Sub plate Note HNBR Aluminum die casted For valve mounting 8 9 Standard Caution M3 0 8 N m M4 1 4 N m M5 2 9 N m Port size How to Order Sub plate...

Page 37: ...3R 18 5 12 1 8 1 4 3 R port X 60 59 24 12 39 19 5 1 8 1 4 1 P port M5 x 0 8 Breathing hole 12 19 5 1 8 1 4 2 A port 12 40 5 18 5 1 8 12 PA port 3R 18 5 12 1 8 1 4 3 R port Series VPA300 Base Mounted...

Page 38: ...1 4 3 8 1 P port M5 x 0 8 Breathing hole NO 2A 1P NC NC 17 6 42 91 47 52 12 6 2 x 5 2 For mounting 13 5 28 5 1 4 3 8 2 A port 12 51 23 1 8 12 PA port 3R 23 13 5 1 4 3 8 3 R port For vacuum VPA544V 1...

Page 39: ...athing hole 3 8 1 2 1 P port 2 x 6 2 For mounting NC NC 1P NO 2A 53 115 1 18 67 66 11 5 X 96 5 95 5 32 5 16 40 80 3 8 1 2 1 P port M5 x 0 8 Breathing hole 16 40 3 8 1 2 2 A port 3R 24 16 3 8 1 2 3 R p...

Page 40: ...ype F N T Rc G NPT NPTF Stations 02 20 2 stations 20 stations Port size 02 03 04 Symbol Port size Applicable series 1 4 3 8 1 2 VPA300 VPA500 VPA700 Description Blanking plate assembly With a gasket a...

Page 41: ...Indicate the valves to be attached below the manifold part number in order starting from station 1 as shown in the drawing VV3PA3 41 051 02 1 set Type 41 5 station manifold base part no VP300 25 1A 1...

Page 42: ...5 16 17 18 19 20 Type 41 Common exhaust VV3PA3 41 1 02 Stations Type 42 Individual exhaust VV3PA3 42 3 02 Stations 12 NC 12 NO 65 2 58 2 65 2 58 2 26 2 26 2 28 7 5 L2 L1 Station n Station 1 N C N O 1...

Page 43: ...Type 42 Individual exhaust VV3PA5 42 3 03 Stations 3R 1P 92 5 30 20 5 60 33 M5 x 0 8 Breathing hole 3 8 1 P 3 R port 12 NC 12 NO 91 83 41 1 91 83 41 1 7 5 31 L1 L2 Station n Station 1 N C N O 1 8 12...

Page 44: ...n exhaust VV3PA7 41 1 04 Stations Type 42 Individual exhaust VV3PA7 42 3 04 Stations 12 NC 12 NO 115 1 107 1 51 5 115 1 107 1 51 5 8 37 L1 L2 N C N O 1 8 12 PA port Pitch P 41 Station n Station 1 2 x...

Page 45: ......

Page 46: ...erator who is appropriately trained and experienced 3 Do not service or attempt to remove product and machinery equipment until safety is confirmed 1 The inspection and maintenance of machinery equipm...

Page 47: ...ease consult your nearest sales branch 2 For any failure or damage reported within the warranty period which is clearly our responsibility a replacement product or necessary parts will be provided Thi...

Page 48: ...wnward with your thumb and pull the connector straight out 2 Crimping lead wires and sockets Strip 3 2 to 3 7 mm at the end of the lead wires insert the ends of the core wires evenly into the sockets...

Page 49: ...it open separating the terminal block and the housing 3 Loosen the terminal screws on the terminal block insert the core of the lead wire into the terminal and attach securely with the terminal screws...

Page 50: ...DC mode type with a surge voltage suppressor polar S and Z types connect wires to terminal 1 and 2 corresponding to the polarity or as shown on the figure on the right 3 Secure the cord by fastening t...

Page 51: ...ge current Leakage voltage Valve R Power DC coil AC coil Especially when a resistor and a switching element are used in parallel or C R device surge voltage suppressor is used for the protection of th...

Page 52: ...Caution With non polar type solenoid valves at times of sudden interruption of the loading power supply such as emergency shutdown surge voltage intrusion may be generated from loading equipment with...

Page 53: ...1 Remove the body from the sub plate and reset the mark on the body corresponding to the N O mark on the sub plate as shown in the figure above 2 Remove the end plate from the body and rotate the end...

Page 54: ......

Page 55: ......

Page 56: ...90 0 212 221 1519 E mail smc entek com tr http www entek com tr Poland SMC Industrial Automation Polska Sp z o o ul Poloneza 89 PL 02 826 Warszawa Phone 48 22 211 9600 Fax 48 22 211 9617 E mail offic...