-23-
No.PF
※※
-OMW0004-A
Mounting and Installation
Installation
Use the product within the specified operating pressure and temperature range.
Proof pressure could vary according to the fluid temperature. Check the characteristics data for operating
pressure and proof pressure.
Mounting
Never mount the product in a place that will be used as a scaffold during piping.
Mount the product so that the fluid flows in the direction indicated by the arrow on the side of the flow switch.
Check the flow characteristics data for pressure loss and the straight inlet pipe length effect on accuracy
(page
), to determine inlet piping requirements.
Do not sharply reduce the piping size.
The monitor with integrated display can be rotated. It can be set at 90
o
intervals clock and anticlockwise, and
also at 45
o
and 225
o
clockwise. Rotating the display with excessive force will damage the end stop.
When the stop valve is mounted, rotate the monitor after closing the stop valve handle.
Rotating the monitor with excessive force while opening the stop valve handle, the monitor and stop valve
will be interfered with each other, which may damage them. (Refer to the figure below)
●
Integrated display type Monitor rotation diagram
Summary of Contents for PF3W504
Page 12: ...11 No PF OMW0004 A Model Indication and How to Order Integrated type Basic type...
Page 13: ...12 No PF OMW0004 A Integrated type Straight type...
Page 14: ...13 No PF OMW0004 A Remote type Supply type...
Page 15: ...14 No PF OMW0004 A Remote type Return type...
Page 55: ...54 No PF OMW0004 A Flow range 2 to 16 L min symbol 20 reference value Nil S P W...
Page 56: ...55 No PF OMW0004 A Flow range 5 to 40 L min symbol 40 reference value Nil S P W...
Page 58: ...57 No PF OMW0004 A Flow range 2 to 16 L min symbol 20 reference value Nil S P W...
Page 59: ...58 No PF OMW0004 A Flow range 5 to 40 L min symbol 40 reference value Nil S P W...