Straight inlet pipe length and accuracy (reference value)
Metal attachment
The smaller the piping size, the more the product is affected by the straight piping length.
Fluid pressure has almost no effect.
The smaller the flow rate, the less the product is affected by the straight piping length.
The straight piping length shall be 8 cm or longer in order to maintain ±3%F.S. of the specification.
Flow range: 0.5 to 4 L/min (symbol 04)
Pressure: 0.3 MPa
Piping bore size:
12
Flow range: 2 to 16 L/min (symbol 20)
Pressure: 0.3 MPa
Piping bore size:
12
Flow range: 5 to 40 L/min (symbol 40)
Pressure: 0.3 MPa
Piping bore size:
16